Branch kit restriction when install
Be sure following restriction.
1) Installation angle
Outdoor unit branch kit
Horizontal
A
To indoor unit
PROHIBITED
A
GOOD:
0° to -10°
PROHIBITED
Vertical
PROHIBITED
• Install the outdoor unit branch kit horizontally level, within 0° to -10°, so that the
refrigerant separates evenly.
• Do not install the outdoor unit branch kit vertically.
2) Straight pipe length
To indoor unit
To outdoor unit
(To main pipe)
0.5 m or more
To indoor unit (To main pipe)
0.5 m or more
• Leave the distance 0.5 m or more for straight part to outdoor unit branch kit.
3) About the connecting curvature of fi eld pipe and branch kit:
The fi eld pipe should be connected to the branch kit so that the curved angle on each
side is 3 degree or less.
*: Allowed value based on "A" (center of
fi eld pipe) at 0.5 m from "B" (junction
of the branch kit).
0.5 m
En-11
Outdoor Capacity
2 Units : Unit 1 ≥ Unit 2
3 Units : Unit 1 ≥ Unit 2 ≥ Unit 3
Joint pipe
(Accessory)
Liquid pipe
(Locally purchased) Gas pipe
(Locally purchased)
To outdoor unit
B
To outdoor unit or
C
next branch kit
PROHIBITED
C
B
GOOD:
C
0° to -10°
PROHIBITED
PROHIBITED
PROHIBITED
To outdoor unit
To outdoor unit
To outdoor unit
To outdoor
unit
4) For details, refer to the Installation Instruction Sheet of the outdoor unit branch kit.
Fig. Examples of multiple unit installation
(Example 1)
Master unit
Slave unit1 Slave unit2
(Example 2)
Master unit
Slave unit1 Slave unit2
To prevent the oil from settling in the stopped unit, install the pipes between the
outdoor units so that they are level or are tilted upward to the outdoor units.
(1) Examples of multiple unit installation are shown below.
a) Installable patterns
Master
Slave
GOOD
unit
unit 1
To indoor unit
Master
Slave
GOOD
unit
unit 1
To indoor unit
Slave
GOOD
Master
unit 1
unit
To indoor unit
b) Non-installable patterns
Master
Slave
PROHIBITED
unit
unit 1
To indoor unit
Master
Slave
PROHIBITED
unit
unit 1
To indoor unit
Master
Slave
PROHIBITED
unit
unit 1
To indoor unit
(2) If the pipe length between outdoor unit branch kit and outdoor unit branch kit
(or slave unit) is longer than 2 m, or a lower pipe line exists between outdoor
units, rise for gas pipe should be arranged to eliminate oil from entering into and
remaining at pipes and the stopped outdoor unit. However, there is no need to
provide a rise on the pipe connecting between the master unit and the indoor unit
even if the length exceeds 2m.
Master
Slave
unit
unit 1
To indoor unit
2 m or less
2 m or less
(Example 3)
Master
unit
Slave
unit1
Slave
unit2
CAUTION
Slave
unit 2
Slave
unit 2
Slave
unit 2
Slave
unit 2
Slave
unit 2
Slave
unit 2
Slave
unit 2