elsner elektronik Sewi AQS/TH Modbus Technical Specifications And Installation Instructions

Indoor sensors

Advertisement

Quick Links

EN
Sewi AQS/TH Modbus
Sewi TH Modbus
Indoor sensors
Technical specifications and installation instructions
Item numbers 30174 (Sewi AQS/TH Modbus), 30175 (Sewi TH Modbus)
1.
Description
The indoor sensors Sewi AQS/TH Modbus and Sewi TH Modbus measure
the indoor temperature and humidity and also calculate the dew point temperatu-
re. The Sewi AQS/TH also records the CO2 concentration.
The devices are Modbus slaves with a RS485 interface and a RTU protocol. The
Modbus master, such as PC, SPS or MC can read the Sewi Modbus Indoor Sen-
sors measurement values with "Function 04h (Read Input Register)".
Sewi TH Modbus Indoor Sensor Functions:
Temperature measurements
Humidity measurements
Calculating the dew point temperature
Sewi AQS/TH Modbus Indoor Sensor Functions:
Measuring the CO2 concentration in the air
Temperature measurements
Humidity measurements
Calculating the dew point temperature
Tips for Dew Point Calculation:
The sensors Sewi Modbus calculate the ambient dew point temperature. This va-
lue can be used for dew point monitoring. This would require another sensor for
measuring the surface temperature of the wall or pipe. Also, the dew point needs
to be monitored (compare with temperatures) in the Modbus master.
Monitoring predetermines the possible condensate build-up on the surface, giving
a chance for timely countermeasures.

1.0.1. Deliverables

Sensor in the housing for wall or ceiling mounting.

1.1. Specifications

Housing
Plastic
Colour
White (Cover glossy, skirting matt)
Assembly
Surface, wall or ceiling installation
Protection category
IP 30
Dimensions
Ø approx. 105mm, height approx. 32mm
Weight
Sewi AQS/TH Modbus: approx. 100g
Sewi TH Modbus: approx. 75g
Ambient temperature
Operation 0 ...+50°C, Storage -20 ...+70°C
Ambient humidity
max. 95% RH, avoid condensation
Operating voltage
24 V DC ±10%.
An appropriate power supply unit can be purchased
from Elsner Elektronik.
Cable cross-section
Solid conductor up to 0.8mm
Power
max. 15mA
Interface
RS485
Protocol
RTU
RS485 bus load
1/8 unit load according to the RS485 standard
RS485 drive output
min. 2.4V at 54 Ohm bus load
(according to the 32 standard RS485 unit loads)
Sewi TH Modbus (30175):
Temperature measure-
-40...+80°C
ment range
Humidity measurement
0% rH ... 100% rH
range
Sewi AQS/TH Modbus (30174):
Temperature measure-
0°C...+50°C
ment range
Humidity measurement
0% rH...90% rH
range
CO
measurement range
100...10,000ppm
2
The product is compliant with the provisions of the EC guidelines.

1.1.1. Measuring accuracy

After applying the operating voltage, it can take up to 15 minutes until the CO
measured value is output correctly.
The CO
sensor uses the last 7 minimum CO
2
ion. These 7 minimum values must be at least 18 hours apart and within the range
of 400 to 450 ppm (fresh air).
2.
Installing and commissioning
Installation, testing, operational start-up and troubleshooting should
only be performed by an authorised electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• Inspect the device for damage before installation. Only put undamaged
devices into operation.
• Comply with the locally applicable directives, regulations and provisions
for electrical installation.
• Immediately take the device or system out of service and secure it against
unintentional switch-on if risk-free operation is no longer guaranteed.
Use the device exclusively for building automation and observe the operating ins-
tructions. Improper use, modifications to the device or failure to observe the ope-
rating instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition
and after conclusion of all installation and operational start-up tasks, and only in
the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.

2.1. Installation location

Install and use only in dry interior rooms!
Avoid condensation.
The indoor sensor is installed on the wall or ceiling plaster.
While selecting the location, please ensure that the temperature, humidity and
CO2 measurements are minimally distorted by external influences as possible.
Possible sources of interference include:
Direct sunlight
Draughts from windows and doors
Draughts from ducts coming from other rooms or the outdoors
Warming or cooling of the building structure on which the sensor is
mounted, e.g. due to sunlight, heating or cold water pipes
Connection lines and empty ducts which lead from warmer or colder areas
to the sensor
3.
Commissioning
Never expose the device to water (e.g. rain) or dust. This can damage the electro-
nics. You must not exceed a relative humidity of 95%. Avoid condensation.
The air slots on the side must not be closed or covered.
After the operating voltage has been applied, the device will enter an initialisation
phase lasting a few seconds. During this phase no information can be received or
sent via the bus.

3.1. Construction of the sensor

3.1.1. Printed circuit boards/connections

ATTENTION!
Make sure the connection is correct!
Connect the power supply to 1 and 2 only.
Use the data connections A and B exclusively for Modbus.
ATTENTION!
CO2 sensor with sensitive membrane in Sewi AQS/TH!
When handling the device, do not damage the white membrane.
2
Sewi Modbus Indoor Sensors • Version: 20.09.2022 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Sewi Modbus Indoor Sensors
values for automatic sensor calibrat-
2
2
1a
2
3
A
4
5
1b
Fig. 1
1 a + b Long holes for mounting (hole distance 60mm)
2 LEDs: Green Power/Operating voltage.
Red Error/Sensor error or incorrect data.
yellow Com/Bus communication.
3 DIP switch for slave address (see detailed view)
4 interface parameter DIP switch (see detailed view)
5 Sensors for temperature, humidity
6 plug for connection, suitable for a solid conductor up to 0.8mm²
1:
24 V DC
(+), 2: GND (-).
Data A: Modbus D0, Data B: Modbus D1.
The reference potential for data lines is GND (-) of the power supply.
7 CO
sensor (only for the Sewi AQS/TH Modbus)
2
8 Cable bushing
A Mark for aligning the cover

3.1.2. Housing from the outside

Fig. 2
A Recess to open the housing.
When closing the housing, the recess aligns to
A
the marking on the skirting

3.2. Assembly

Fig. 3
Open the housing. To do this, carefully lift the
cover from the skirting. Start at the recess (Fig.
2: A).
Fig. 4
Lead the power cable through the cable bus-
hing in the skirting.
Fig. 5
Screw the skirting to the wall or the ceiling.
Hole distance 60mm.
Fig. 6
Connect the power supply
1 (+)/2 (GND, -) and data lines
A (Modbus D0) / B (Modbus D1)
to their designated terminals.
The reference potential for data lines is GND (-)
of the power supply.
ATTENTION!
Make sure the connection is correct!
Connect the power supply to 1 and 2 only.
Use the data connections A and B exclusively for Modbus.
Fig. 7
Close the housing by positioning the cover and
snapping it into place. Position the recess in the
cover over the marking on the skirting (Fig. 1+2:
A).
1
6
7
8

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Sewi AQS/TH Modbus and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for elsner elektronik Sewi AQS/TH Modbus

  • Page 1 The product is compliant with the provisions of the EC guidelines. Sewi Modbus Indoor Sensors • Version: 20.09.2022 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250...
  • Page 2 Temperature xx.x°C Temperature Low Byte Sewi Modbus Indoor Sensors • Version: 20.09.2022 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250...

This manual is also suitable for:

Sewi th modbus3017430175

Table of Contents