elsner elektronik Sewi KNX L-Pr Installation And Adjustment

Presence detector with brightness sensor

Advertisement

Quick Links

EN
Sewi KNX L-Pr
Presence detector with
brightness sensor
Item numbers 70396 (white), 70696 (jet black)
Installation and Adjustment

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Sewi KNX L-Pr and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for elsner elektronik Sewi KNX L-Pr

  • Page 1 Sewi KNX L-Pr Presence detector with brightness sensor Item numbers 70396 (white), 70696 (jet black) Installation and Adjustment...
  • Page 3: Table Of Contents

    8.9.2. AND logic connection inputs ..............38 8.9.3. Connection inputs of the OR logic ............. 40 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Sensor Sewi KNX L-Pr • from application 1.1 Version 26.10.2021 • Errors excepted. Subject to technical changes.
  • Page 4 Clarification of signs This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service"...
  • Page 5: Description

    Description Description The Sensor Sewi KNX L-Pr for the KNX building bus system captures brightness and the presence of persons in rooms. The brightness value measured can be used for the control of limit-dependent switching outputs. States can be linked via AND logic gates and OR logic gates.
  • Page 6: Safety And Use Instructions

    • Comply with the locally applicable directives, regulations and provisions for electrical installation. • Immediately take the device or system out of service and secure it against unintentional switch-on if risk-free operation is no longer guaranteed. Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 7: Installation

    Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions. Installation 3.1.
  • Page 8: Connection

    The Sensor Sewi KNX L-Pr is surface-mounted but at the same time can also be screwed to a flush-mounted socket. If the Sensor Sewi KNX L-Pr is installed on a flush-mounted socket, it must not con- tain any wiring with 230 V.
  • Page 9: Assembly

    Fig. 5 Lead the bus cable through the cable bushing in the skirting. Fig. 6 Screw the skirting to the ceiling. Hole distance 60 mm. Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 10: Commissioning

    As a rule, it is sufficient to wipe the device with a soft, dry cloth twice a year. Disposal After use, the device must be disposed of in accordance with the legal regulations. Do not dispose of it with the household waste! Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 11 Disposal Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 12: Transfer Protocol

    -WC- [7.5] DPT_Time- 2 bytes value 2: Delay from 1 to 0 PeriodSec Brightness sensor 2 threshold Output R-CT [1.1] DPT_Switch 1 bit value 2: Switching output Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 13 Depending on 4 bytes setting 1145 Computer 1: Output O2 Output R-CT Depending on 4 bytes setting 1146 Computer 1: Condition text Output R-CT [16.0] DPT_String_ASCII bytes Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 14 R-CT Depending on 4 bytes setting 1170 Computer 4: Condition text Output R-CT [16.0] DPT_String_ASCII bytes 1171 Computer 4: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 15 R-CT [16.0] DPT_String_ASCII bytes 1195 Computer 7: Monitoring status Output R-CT [1.1] DPT_Switch 1 bit 1196 Computer 7: Block (1: block) Input -WC- [1.1] DPT_Switch 1 bit Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 16 1416 AND logic 2: 8-bit output A Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount 1417 AND logic 2: 8-bit output B Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 17 1444 OR logic 1: 8-bit output A Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount 1445 OR logic 1: 8-bit output B Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 18 1472 OR logic 8: 8-bit output A Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount 1473 OR logic 8: 8-bit output B Output R-CT [5.010] DPT_- 1 byte Value_1_Ucount Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 19 1547 Motion detector: Master 2: Slave Input -WC- [1.1] DPT_Switch 1 bit message 1548 Motion detector: Master 2: Slave Output --CT [5.1] 1 byte cycle reset DPT_Scaling Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 20 1570 Motion detector: Master 4: Central off Input -WC- [1.1] DPT_Switch 1 bit 1581 Light controller: Brightness setpoint Input/ RWCT [9.4] DPT_Val- 2 bytes value Output ue_Lux Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 21: Parameter Setting

    Behaviour on bus restoration of power and following programming or reset: The device sends all outputs according to their send behaviour set in the parameters with the delays established in the "General settings" parameter block. Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 22: General Settings

    0 • 1 [depending on the type of test object] Test object value without movement e.g. 0 • 1 [depending on the type of test object] Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 23: Master 1/2/3/4

    If the device is set as a master, the additional master settings 1 to 4 will appear. This enables the Sensor Sewi KNX L-Pr to perform four different control functions for motion detection. Activate the master in order to use it.
  • Page 24 Then specify the switch-on value. This is the value, below which the room should be lit in the event of movement. Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 25 • 4 byte counter with math. symbol • 4 byte floating point Output value in the event of motion e.g. 0 • 1 [depending on the output type] Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 26 "master: slave message" and evaluates the sla- ve message as an own sensor message. Furthermore, the master has the possibility of triggering a reset of the slave sending cycle. Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 27: Align Communication Between Master And Slave

    A person steps into a corridor, the master recognises this movement and switches on the corridor lighting. When leaving the corridor, the person wants to switch off the light using a switch. Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 28: Light Control

    (via the activated switching object) or a dim value can be sent. Regulation starts on • movement • reception of a start/stop-object • reception of a start/stop-object or movement Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 29 Set, which objects will trigger interruption and when the regulation is to be continued. Use interruptions No • Yes Interrupt regulation when Reception from response switching object No • Yes Reception from response dimming object No • Yes Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 30: Brightness Measurement

    • send off command • send on command • send value 8.5. Brightness Measurement The Sensor Sewi KNX L-Pr detects the brightness in rooms, for example for control- ling lights. Set the sending pattern for the measured brightness. Sending pattern • never •...
  • Page 31: Brightness Threshold Values

    • after power supply restoration and programming Select whether the threshold value is to be specified per parameter or via a communi- cation object. Threshold value setpoint using Parameter • Communications object Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 32 • on change and periodically • on change to 1 and periodically • on change to 0 and periodically Cycle 5 s ... 2 h (if sent periodically) Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 33: Night

    (setting via objects is ignored). Maintain the delays received via communication objects • never • after power supply restoration • after power supply restoration and programming Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 34: Computer

    (setting via objects is ignored). Maintain the input values received via communication • never objects • after power supply restoration • after power supply restoration and programming Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 35 • 4 byte counter without math. symbol • 4 byte counter with math. symbol • 4 byte floating point Output value (if applicable output value A1 / A2) Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 36 0 [Input range depending on the type of is exceeded output] if blocked 0 [Input range depending on the type of output] Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 37 No • Yes Analysis of the blocking object • At value 1: block | At value 0: release • At value 0: block | At value 1: release Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 38: Logic

    Each logic output may transmit one 1 bit or two 8 bit objects. Determine what the out put should send if logic = 1 and = 0. Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 39 0 … 255 / 100% / 360° / 127; 0 monitoring period is exceeded Output value object B if 0 … 255 / 100% / 360° / 127; 0 monitoring period is exceeded Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 40: And Logic Connection Inputs

    Output behaviour on exceeding the moni- • Do not send message toring time • Send value exceeding [= value of the parameter "monitoring period"] 8.9.2. AND logic connection inputs Do not use Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 41 Motion detector test output active Motion detector test output inactive Motion detector test output active Motion detector test output inactive Motion detector slave output active Motion detector slave output inactive Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 42: Connection Inputs Of The Or Logic

    Switching output AND logic 6 inverted Switching output AND logic 7 Switching output AND logic 7 inverted Switching output AND logic 8 Switching output AND logic 8 inverted Sensor Sewi KNX L-Pr • Version: 26.10.2021 • Technical Changes and Errors excepted.
  • Page 44 Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone +49 (0) 70 33 / 30 945-0 info@elsner-elektronik.de Germany +49 (0) 70 33 / 30 945-20 www.elsner-elektronik.de Technical support: +49 (0) 70 33 / 30 945-250...