Samsung AEX160EDEHA Service Manual page 10

Table of Contents

Advertisement

Product Specifications (cont.)
Item
Image
Outdoor unit
Heating 1
Heating 2
Capacity (95%↑)
Cooling 1
Cooling 2
Heating 1
POWER
Heating 2
CONSUMPTION
Cooling 1
(110%↓)
Cooling 2
Heating 1
Heating 2
Running Current
(110%↓)
Cooling 1
Cooling 2
Power Supply
Heating 1
Heating 2
COP/EER (95%↑)
Cooling 1
Cooling 2
Refrigerant Charge
Net
Set Dimensions
Gross
(W*H*D)
Weight
(Net/Gross)
Cooling
Cond.1/2
Noise
Heating
Cond.1/2
Cooling
Operation
range
Heating
Samsung Electronics
AEX160EDEHA
AEX140EDEHA
1phase 16kW
1phase 14kW
W
16,000
14,000
W
15,000
13,000
W
17,400
16,200
W
13,300
12,300
W
3,720
3,110
W
4,410
3,710
W
6,000
5,150
W
5,420
4,730
A
16.3
13.7
A
19.4
16.3
A
26.4
22.6
A
23.8
20.8
Ø,V,Hz
1 / 220-240 / 50
1 / 220-240 / 50
W/W
4.30
4.50
W/W
3.40
3.50
W/W
2.90
3.15
W/W
2.45
2.60
g, type
2,800 R410A
2,800 R410A
mm
940X1,420X330
940X1,420X330
mm
995X1,548X426
995X1,548X426
kg
98 / 108
98 / 108
dB(A)
61
60
dB(A)
60
59
10~46
10~46
-20~35
-20~35
AEX125EDEHA
AEX100EDEHA
1phase 12.5kW
1phase 10kW
12,500
10,000
11,500
9,500
15,000
9,100
11,300
7,100
2,660
2,220
3,195
2,750
4,350
2,890
4,110
2,730
11.7
9.7
14.0
12.1
19.1
12.7
18.1
12.0
1 / 220-240 / 50
1 / 220-240 / 50
4.70
4.50
3.60
3.45
3.45
3.15
2.75
2.60
2,800 R410A
2,000 R410A
940X1,420X330
940X998X330
995X1,548X426
995X1,096X426
98 / 108
74 / 82
59
59
59
57
10~46
10~46
-20~35
-20~35
General Overview
AEX060EDEHA
1phase 5.8kW
5800
5300
6670
4900
1220
1490
1905
1810
5.7
7.0
8.8
8.1
1 / 220-240 / 50
4.75
3.56
3.5
2.7
1,200 R410A
880X638X310
1024X750X414
48 / 53
54
53
10~46
-20~35
9