3. Operation

3.1 Transport Mode

Sensors are shipped with a plastic battery insulating pull tab that must be removed before the
operation.

3.2 Default Operation

During default operation, the device will send an environmental status message to the network
once there is a sufficient delta in the environmental conditions or 5 minutes of inactivity. The
precise trigger values can be found in 4.1.1.

4. Messages

LoRaWAN Packets for this device use port 103.

4.1 Status

4.1.1 Triggers

Packet Triggers: 5-minute inactivity, ±2°C delta(environment temp), ±5 %RH
Delta, ±25 IAQ Index Delta. ​ T he device will scan the environment every 5 
minutes.

4.1.2 Payload

Port
Payload Length
Bytes
0
Field
Status
© 2019 Browan Communications Inc. All rights reserved.
103
11 bytes
1
2
3
Battery
Temp.
RH
(PCB)
4
5
6
7
CO​
VOC
2
8
9
10
IAQ
Temp.
(environment)