AX03
Dimensions AX03
3
FHF B 6030-10
04/11
118
89
102

Installation

The sounder can be affixed to most surfaces using
screws through the external mounting lugs. A 20 mm
gland entry is provided for the supply cable. The cable
and gland must be fitted in accordance with the national
and local regulations. It is not necessary to earth the
sounder circuitry but earth tags should be used if earth
continuity of conduit or cable sheathing needs to be
maintained.

Supply input

Ensure that the supply is correct for the voltage rating of
the sounder. Ensure that the supply is OFF before
making any connection and wire only in accordance
with the terminal label detail.

Sound selection

Ensure the supply is OFF before proceeding. All dc and
ac units have selectable alarm sounds (see table below
for details) and are selectable by means of the 5 way
DIL switches SW1 for the first stage and SW2 for the
second stage. For dc units the second sound is made
available upon the application of a third wire connected
to terminal TB 1/3 as shown in Fig. 1 while still connec-
ted to terminal TB 1/2. Alternatively first and second sta-
ge sound signals can be generated by supply reversal at
terminals TB1/3 and TB1/4, see Fig. 2. For ac units the
second stage is available upon the application of a third
wire L to TB3, see Fig. 3.

Mounting

The AX03 series alarm units are mounted to a wall or
bulkhead of suitable material using the lugs projecting
from the side of the case. The lugs are bored 6 mm cle-
arance on 102 mm centres. The recommended length
of fixing screws is 20 mm. To maintain the integrity of
the weather seal, the cable entry must be via a suitable
sealed gland.

Recycling

The device may be completely recycled as electronic
waste. When the device is disassembled, plastics,
metals and electronics are to be disposed of separately.
EM -Directive
The device complies with the requirements of the
new EMC-directive 2004/108/EC and the low voltage
directive 2006/95/EC.
The conformity with the above directives is confirmed
by the CE sign.
Sounder
AX03
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AVISA AX03 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for FHF AVISA AX03

  • Page 1 EM -Directive The device complies with the requirements of the new EMC-directive 2004/108/EC and the low voltage directive 2006/95/EC. The conformity with the above directives is confirmed by the CE sign. FHF B 6030-10 04/11...
  • Page 2 Technical Data Housing Polycarbonate Colour Red, similar to RAL 2002 Insulation class Protection degree IP 65 acc. to IEC 60529 Cable gland intended for M20 x 1.5 or Self-sealing grommet Volume approx. 97-110 dB(A) (depending on signal tone) Signals 32 different signal tones, see diagrams 2nd stage can be turned on externally Temperature range Operation...
  • Page 3 Figure 1 Figure 2 DC Input - second stage with third wire DC Input - second stage by supply reversal Line integrity: monitor via reverse polarity Line integrity: monitor via threshold (applied voltage 1 V) An end-of-line (E.O.L) resistor is required for line monitoring and it should be a minimum resistance of 3K3 ohms and 0.5 watts.
  • Page 4 The use of other than original spare parts may cause damage or injury. Subject to alterations or errors FHF Funke + Huster Fernsig GmbH Gewerbeallee 15-19 · D-45478 Mülheim an der Ruhr Phone +49 / 208 / 82 68-0 · Fax +49 / 208 / 82 68-286...

Table of Contents