2. Safety
2.6

Installation precautions

2.6.1 Installation site precautions

Do not install machines or equipment near heat sources, in areas at risk with explosion hazard or fire
hazard.
Install the machine at a safe distance from fuel tanks, from flammable material (rags, paper, etc.), from
chemicals.
Follow the instructions of the competent authorities.
To limit potentially dangerous situations, isolate the area around the generating set, thus preventing any
unauthorized personnel from getting close to it.
Although the machines produced comply with the regulations on electromagnetic compatibility, do not
install the unit near equipment influenced by the presence of magnetic fields.
Make sure that the area immediately surrounding the machine is clean and free of debris.
Always place the machine on a flat, solid surface that is not subject to failure in order to avoid tipping,
slipping or falling during operation.
Avoid using the machine on land with a slope greater than 10°.
The machine must always be positioned so that exhaust
gases disperse into the air without being inhaled by
people or animals.
The exhaust gases of an engine contain carbon mon-
oxide: this substance is harmful to health and, in high
concentration, can cause poisoning and death.
If the machine is used indoor, the installation should be
designed by specialized technicians and carried out in a
workmanlike manner.
The guard used to protect the generating set must not prevent the required normal cooling of the compo-
nents.

2.6.2 Precautions for open generating sets (SKID)

Open machines (SKIDS) must be installed on pitches protected against atmospheric agents such as rain,
snow, high humidity and direct exposure to the sun.
If the alternator of the machine comes into contact with water or high humidity, especially during opera-
tion, the voltage supplied can rise beyond the limits, winding failures, electrical discharges towards the
ground with damage to the machine, to the user systems and danger to people.
Prevent the generating set from coming into contact with dust, especially of a saline nature.
If the radiator or the intake filters of the engine or the radiator are clogged with particles present in the air,
there is the risk that the generating set will overheat and become damaged.
Make sure that the suction grilles are not clogged with leaves, snow or other materials.

2.6.3 Precautions for electric connections

Connect the machine to a grounding system according
to the regulations in force at the place of installation.
Use the ground terminal located on the front of the ma-
chine.
Use appropriate electrical plugs at the machine output
sockets and make sure that the electrical cables are in
good condition.
Do not use the machine with wet or damp hands and/or
clothing.
D5260150
D5260160
13

Advertisement