Type of
Switch No.
Switch
1
2
SW5
3,4,5
6
1
2
3
Max Hz setting (cooling)
SW7*
4
4
Max Hz setting (heating)
5
Breaker capacity setting *
6
1
SW8
2
3
1
SW9
2
3,4
1
2
DIP
3
switch
4
5
6
7
SW6
8
*
2
'Power failure automatic recovery' can be set by either remote controller or this DIP SW. If one of them is set to ON, 'Auto
recovery' activates. Please set "Auto recovery" basically by remote controller because all units do not have DIP SW.
Please refer to the indoor unit installation manual.
*
3
SW7-1 is setting change over of Demand/Low noise. It is effective only in the case of external input.
(Local wiring is necessary. Refer to the next page: Special function)
*
4
Please do not use SW7-3 to 7-6 usually. Trouble might be caused by the usage condition.
*
5
With this switch setting, the capacity decreases up to 30% under peak load condition. (Only ZM60-140V)
*
6
SW6-1 to 3: Function switch
OCH771C
Function
No function
Power failure
automatic recovery *
2
No function
No function
Mode select *
3
No function
Max Hz (cooling) × 0.8
Max Hz (heating) × 0.8
5
Defrost setting
No function
No function
No function
Fan motor switch
Function switch
No function
Defrost after turning off
No function
Model select
Action by the switch operation
ON
—
Auto recovery
No auto recovery
—
—
Demand function
Low noise mode
—
Decrease capacity
For high humidity
—
—
—
High static pressure
Valid
—
—
—
The black square (■) indicates a switch position.
MODEL
SW6 *
6
ON
60
OFF
1 2 3 4 5 6 7 8
ON
71
OFF
1 2 3 4 5 6 7 8
MODEL
SW6 *
6
MODEL
ON
ON
100V
OFF
OFF
100Y
1 2 3 4 5 6 7 8
ON
ON
125V
OFF
125Y
OFF
1 2 3 4 5 6 7 8
ON
ON
140V
OFF
140Y
OFF
1 2 3 4 5 6 7 8
SW6 *
MODEL
6
ON
OFF
200
1 2 3 4 5 6 7 8
ON
250
OFF
1 2 3 4 5 6 7 8
76
Effective timing
OFF
—
When power supply ON
—
—
Always
—
Normal
Always
Normal
Always
Normal
When power supply ON
Normal
Always
—
—
—
Normal
When power supply ON
Normal
Always
—
Valid
When power supply ON
—
SW6 *
6
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
—
—
—
—
—
—
—
—
—