Dimensions

Mounting holes: ø7
147
OUT IN
Drain
116
Applicable cable
144
diameter: ø6 to 8
30
259
200
16
35
Mounting pitch: 230
(Unit: mm)
11

Digital communications

◆Communication Method
Item
Description
Compliant Standard
Based on EIA RS-485
Transmission Method
2-wire, semi-duplicate
MODBUS RTU 1 (default)
OM1
MODBUS ASCII 1
MODBUS RTU 2
Protocol
OM2
MODBUS ASCII 2
TC-Mi protocol
Baud rate
9600 (default) / 14400 / 19200 / 38400 bps
Data bits
8 bit
Start bits
1 bit
Stop bits
1 bit
Parity bit
None (default) / Odd / Even
Slave address
1 (default) to 247
MODBUS only
1

MODBUS protocol

◆Frame Configuration
Mode
Start
Slave address
RTU
1 byte
ASCII
2 chars
Item
Mode
RTU
3.5 chare silence
Start
ASCII
":"character
3.5 chare silence
RTU
End
ASCII
"CR","LF" character
1 to 247
Slave address
Common
OM1 RTU/ASCII
4, 6
Function code
OM2 RTU/ASCII
3,16
RTU
0-N bytes with response data from the device.
Data
0-N bytes with response data from the device in hex characters.
ASCII
RTU
CRC
Error check
ASCII
LRC
Mode
Function Code
4
Read registers.
OM1
6
Write resisters.
3
Read registers.
OM2
16
Write resisters.
Function code
Error check
Data
1 byte
n byte
2 byte
2 chars
n chars
2 chars
Description
Description
End
CR, LF
31