en | Test procedure
4.4

Smoke and flame detection (test video)

Figure 4.5: Test setup (smoke and flame detection, test video)
1.
2.
3.
ð
Enter the results in the commissioning report.
2023-10 | 01 | F.01U.414.170
Place a playback device (computer monitor or a tablet) in the detection area in front of
the camera.
Align the monitor to the test camera.
Play the video for smoke and flame detection.
A smoke alarm shall be triggered within the set smoke verification time plus 15 s. A
flame alarm shall be triggered within the set flame verification time plus 15 s. A
connected video client shall show a rectangular box around the smoke region and one
around the flame region.