  • Page 1 AVIOTEC 8000i IR FCS‑8000‑VFD‑I Commissioning...
  • Page 3: Table Of Contents

    AVIOTEC 8000i IR Table of contents | en Table of contents Safety Safety message explanation Safety precautions Introduction Required test equipment Real smoke test equipment Smoke and flame video test equipment Test procedure Smoke detection (real smoke) Smoke detection (test video)
  • Page 4: Safety

    In addition, and for the U.S. market only, Bosch Security Systems makes no representation that the video fire indication system will prevent any personal injury or property loss by fire or otherwise;...
  • Page 5 AVIOTEC 8000i IR Safety | en Danger! Toxic gas Avoid the inhalation of toxic products or smoke. Stay away from the test area unless otherwise instructed. Warning! Fire hazard Only use the specified test equipment. Warning! Personal injury and property damage Follow all safety information and user documentation including test equipment documents and safety instructions to avoid personal injuries and property damage.
  • Page 6: Introduction

    | Introduction AVIOTEC 8000i IR Introduction Copyright The manufacturer retains the complete copyright to the whole documentation and assumes no liability for damage or malfunction arising through failure to comply with this document. This document is aimed at readers with know-how and experience in planning and installing EN 54‑compliant fire alarm systems who have additional fire and smoke testing knowledge.
  • Page 7: Required Test Equipment

    AVIOTEC 8000i IR Required test equipment | en Required test equipment The illumination is measured using a luxmeter in the application at a height of 1 meter with the sensor pointing vertically upwards. The following material is needed during the tests and is defined for one camera.
  • Page 8: Test Procedure

    | Test procedure AVIOTEC 8000i IR Test procedure Preparation of the test scene Ensure that the camera is properly installed. For functional testing, existing fire alarm systems and detectors must be switched to revision mode. This also applies to fire alarm systems in which the customer might have integrated the camera directly to the fire panel.
  • Page 9: Smoke Detection (Real Smoke)

    AVIOTEC 8000i IR Test procedure | en Smoke detection (real smoke) Figure 4.2: Test setup (smoke detection, real smoke generated by smoke cartridges) Put the fireproof metal bucket on solid and fireproof ground. Position two smoke cartridges upright into the metal bucket.
  • Page 10: Smoke Detection (Test Video)

    | Test procedure AVIOTEC 8000i IR Smoke detection (test video) Figure 4.3: Test setup (smoke detection, test video) Place a playback device (computer monitor or a tablet computer) in the detection area in front of the camera. Align the monitor to the test camera.
  • Page 11: Flame Detection (Test Video)

    AVIOTEC 8000i IR Test procedure | en Flame detection (test video) Figure 4.4: Test setup (flame detection, test video) Place a playback device (computer monitor or a tablet computer) in the detection area in front of the camera. Align the monitor to the test camera.
  • Page 12: Smoke And Flame Detection (Test Video)

    | Test procedure AVIOTEC 8000i IR Smoke and flame detection (test video) Figure 4.5: Test setup (smoke and flame detection, test video) Place a playback device (computer monitor or a tablet) in the detection area in front of the camera.
  • Page 13: Commissioning Report

    AVIOTEC 8000i IR Commissioning report | en Commissioning report Camera installation and configuration protocol General Camera name (Configuration -> General - > Identification) Firmware version (Configuration -> Service -> System Overview) Date/Time setting o Synchronized (Configuration -> General -> Date/Time) Mounting height Field of view (Please add a screenshot) Screenshot location (e.g. network folder)
  • Page 14 | Commissioning report AVIOTEC 8000i IR (Configuration -> Camera -> Installer Menu -> Open... -> Focus indicator) Optical lens Position: Opening angle: Network settings IP address (Configuration -> Network -> Network Access) Connection IP connection tested o Yes     o No Relay connected to Alarm Relay tested o Yes     o No Alarm Relay Idle state o CLOSED     o OPEN Trouble Relay tested o Yes     o No...
  • Page 15 AVIOTEC 8000i IR Commissioning report | en Privacy Masks o Yes     o No (Please add a screenshot) VFD Settings Fire#1 Flame detection o On     o Off (Configuration -> Alarm -> Fire detection) Sensitivity o low     o mid     o high Verification time [s] Smoke detection o On     o Off (Configuration -> Alarm -> Fire detection) Sensitivity o low     o mid     o high Verification time [s] Masks (smoke, flame, smoke time o Yes     o No...
  • Page 16 | Commissioning report AVIOTEC 8000i IR Privacy Masks o Yes     o No (Please add a screenshot) VFD Settings Fire#2 Flame detection o On     o Off (Configuration -> Alarm -> Fire detection) Sensitivity o low     o mid     o high Verification time [s] Smoke detection o On     o Off (Configuration -> Alarm -> Fire detection) Sensitivity o low     o mid     o high Verification time [s] Masks (smoke, flame, smoke time o Yes     o No...
  • Page 17 AVIOTEC 8000i IR Commissioning report | en Privacy Masks o Yes     o No (Please add a screenshot) Used fire profile o Fire     o Fire#1     o Fire#2 Scheduler used o Yes     o No Scheduling plan (please add a screenshot of the scheduler configuration in Configuration manager) Bosch Sicherheitssysteme GmbH 2023-10 | 01 | F.01U.414.170...
  • Page 18 | Commissioning report AVIOTEC 8000i IR Event triggered used o Yes     o No Trigger Profile used if trigger active Profile used if trigger inactive Delay Tamper detection settings Scene too bright threshold Scene too dark threshold Reference image set o Yes     o No (Please add screenshot)
  • Page 19 AVIOTEC 8000i IR Commissioning report | en Installation conditions / application Scene illumination Check the minimum illuminance is ≥ 1 lx o Yes     o No    Min. Illuminance:                    lx Check if illumination in B/W mode with o Yes     o No IR-illuminators is sufficient Check if Day/Night setting is correct o Yes     o No...
  • Page 20 | Commissioning report AVIOTEC 8000i IR Obstructions in the picture taken into o Yes     o No account Smoke test results (smoke cartridges) Day/Night Color Monochrome Distance to smoke cartridge Illumination Smoke cartridge(s) Smoke detected o Yes     o No o Yes     o No Field of view (Please add a screenshot)
  • Page 21 AVIOTEC 8000i IR Commissioning report | en Smoke/flame test results (test video) Day/Night Color Monochrome Distance to monitor Illumination Smoke detected o Yes     o No o Yes     o No Flame detected o Yes     o No o Yes     o No Field of view (Please add a screenshot) Place: Issuer: Date: Signature: Bosch Sicherheitssysteme GmbH 2023-10 | 01 | F.01U.414.170...
  • Page 22 | Commissioning report AVIOTEC 8000i IR 2023-10 | 01 | F.01U.414.170 Bosch Sicherheitssysteme GmbH Commissioning...