Electrical Connections; Refrigerant Charge - Carrier AQUASNAP 30RB 017-040 A Installation, Operation And Maintenance Manual

Air-cooled liquid chillers and reversible cycle air-water heat pump with integrated hydraulic module
Table of Contents

Advertisement

30RB/30RQ - 30RBY
Electrical connections and refrigerant charge

Electrical connections

CAUTION:
To prevent electrical shock or equipment damage, make sure disconnects
are open before electrical connections are made.
Power supply cable size and external connection must be made by
the installer according to the unit installation characteristics and the
applicable standards. The power supply and earth multicore cable of
the device has to be connected to the general disconnector by routing
the cable through the grommet installed in the device, after removing
the access panel/s. The maximum section allowable for flexible copper
cable is 25 mm
2
. Before connection, check that phase sequence
L1 – L2 – L3 is correct. The table below should be considered as a reference
and does not involve Carrier responsibility.
30RB/30RQ
30RB/30RQ
Unit
017
021
Cable section
5 x2.5 mm²
Power supply
cable
Fuse (type "gG") 25 A
32A
Take special care when making the earth connection.
The maximum permitted voltage and current imbalance is 10% of the
values indicated in Table II.
Contact your local power company for correction of an incorrect line
voltage.
CAUTION:
Operation of the unit on improper line voltage constitutes abuse and is
not covered by the Carrier warranty.
IMPORTANT:
To ensure the correct unit power supply (cable entry, conductor cross
section, protection devices etc.), consult the electrical data table, the wiring
diagram supplied with the unit and the applicable standards concerning
the installation of air conditioning equipment.
Never operate a unit if the voltage imbalance exceeds 2%.
The following formula must be used to determine the percentage of
voltage imbalance.
Voltage imbalance (%) =
Largest deviation from average voltage x 100
———————————————————————————-
Average voltage
Example:
Supply voltage: 400-3-50
AB =
404 V
BC =
399 V
AC =
394 V
Average voltage = 404 + 399 + 394 = 399 ≈ 400 V
3
Determine maximum deviation from average voltage:
AB =
404 - 400 = 4
BC =
400 - 399 = 1
AC =
400 - 394 = 6
Largest deviation is 6 volts. Percentage voltage imbalance is therefore:
6
x 100 = 1.5 %
400
CAUTION:
The installer must install protection devices, as required by the
applicable legislation.
For sizes 17-21 kW, the power supply cable must be routed through the
grommet of the electric control panel. To connect the power supply cable
to the main disconnector remove the metal protection box (by removing
the two fixing screws). After completing all connections, re-install the
protection box by fixing the two screws which were previously removed.
The liquid level gauge can be checked by removing the plug from the side
panel (there is no need to remove the whole panel).
15
30RB/30RQ
30RB/30RQ
30RB/30RQ
026
033
040
5 x4 mm²
1x16 mm²
H07 RN-F
40 A
50 A
63A
Motor
The protection level of all the control boxes is IPX4.
Liquid refrigerant charge
Important information regarding the refrigerant used:
This product contains fluorinated greenhouse gas covered by the Kyoto
protocol.
Fluid type: R410A
Global Warming Potential (GWP): 2088
CAUTION:
1. Any intervention on the refrigerant circuit of this product should be
performed in accordance with the applicable legislation. In the EU, the
regulation is called F-Gas, N°517/2014.
2. Ensure that the refrigerant is never released to the atmosphere during
installation, maintenance or equipment disposal.
3. The deliberate gas release into the atmosphere is not allowed.
4. If a refrigerant leak is detected, ensure that it is stopped and repaired
as quickly as possible.
5. Only a qualified and certified personnel can perform installation
operations, maintenance, refrigerant circuit leak test as well as the
equipment disposal and the refrigerant recovering.
6. The gas recovery for recycling, regeneration or destruction is at
customer charge.
7. Periodic leak tests have to be carried out by the customer or by third
parties. The EU regulation set the periodicity here after:
System WITHOUT leakage detection No Check 12 Months
System WITH leakage detection
Refrigerant charge/circuit
(CO
equivalent)
2
R134A
(GWP 1430)
R407C
(GWP 1774)

Refrigerant charge/

Circuit (kg)
R410A
(GWP 2088)
HFO's:
R1234ze
* From 01/01/2017, units must be equipped with a leakage detection system
8. A logbook must be established for equipments subject to periodic
leak tests. It should contain the quantity and the type of fluid present
within the installation (added and recovered), the quantity of recycled
fluid, regenerated or destroyed, the date and output of the leak test,
the designation of the operator and its belonging company, etc.
9. Contact your local dealer or installer if you have any questions.
Checking the charge
CAUTION:
Accidental exhaust of refrigerant, whether due to a small leak or to a
large discharge from a piping rupture, can cause frostbites and burns
to the exposed person. Never neglect such injures. The installers,
owners and especially the repairers for small outdoor units, must:
- set a procedure to consult medical experts prior to treat such injuries,
- provide first aid equipments, especially for rapid treatment of eye
injuries.
We recommend them to apply the EN 378-3 Annex 3.
When adjusting the refrigerant charge, always ensure that water is
circulating in the heat exchanger to prevent any possibility of freezing
up. Damage caused by freezing is not covered by the product warranty.
6 Months
6 Months
No Check 24 Months 12 Months
6 Months
5 ≤ Charge
50 ≤ Charge
Charge > 50
< 5 Tons
< 50 Tons
< 500 Tons
3.5 ≤
34.9 ≤
Charge <
Charge >
Charge <
Charge <
3.5 kg
349.7 kg
34.9 kg
349.7 kg
2.8 ≤
28.2 ≤
Charge <
Charge >
Charge <
Charge <
2.8 kg
281.9 kg
28.2 kg
281.9 kg
2.4 ≤
23.9 ≤
Charge <
Charge >
Charge <
Charge <
2.4 kg
239.5 kg
23.9 kg
239.5 kg
no requirement