LA SORTIE UPS
Spécification du disjoncteur
MBS100D5B
Voltage nominal
Phase
Courant nominal
Pouvoir de coupure
Pôle
MBS175D5B
Voltage nominal
Phase
Courant nominal
Pouvoir de coupure
Pôle
4. SCHÉMA DE CÂBLAGE MBS
Q1 ENTRÉE UPS
L1
L2
L3
N
G
SORTIE UPS
L1
L2
L3
N
ENTRÉE
DISJONCTEUR (Q1)
240 Vca
Triphasé
100 A
50 kA
3 pôles
ENTRÉE
DISJONCTEUR (Q1)
240 Vca
Triphasé
175 A
50 kA
3 pôles
DÉRIVATION
Q2
Q3
ENTRETIEN
DISJONCTEUR DE
DÉRIVATION (Q2)
240 Vca
Triphasé
100 A
50 kA
4 pôles
ENTRETIEN
DISJONCTEUR DE
DÉRIVATION (Q2)
240 Vca
Triphasé
175 A
50 kA
4 pôles
25
L1
L2
VERS
DÉRIVATION
L3
ENTRÉE UPS
N
G
L1
L2
L3
CHARGER
N
G
SORTIE
DISJONCTEUR (Q3)
240 Vca
Triphasé
100 A
50 kA
4 pôles
SORTIE
DISJONCTEUR (Q3)
240 Vca
Triphasé
175 A
50 kA
4 pôles