Download Print this page

Carrier 38BYC Installation And Start-Up Instructions Manual page 4

12 seer split system heat pump

Advertisement

UNIT
SiZE
018
O24
030, 036
O42
048, 060
NOTES:
Table 1--Refrigerant
Connections
And Recommended
Liquid= And Vapor=Tube Diameters
(in.)
LBQUID
VAPOR
VAPOR
(LONG
LINE)
Connection
Diameter
Tube Diameter
Connection
Diameter
Tube Diameter
Connection
Diameter
Tube Diameter
3/8
3/8
5/8
5/8
5/8
3/4
3/8
3/8
3/4
3/4
3/4
3/4
3/8
3/8
3/4
3/4
3/4
7/8
3/8
3/8
7/8
7/8
7/8
1-1/8
3/8
3/8
7/8
1-1/8
7/8
1-1/8
1 Tube diameters
are for lengths up to 50 ft. For tubing _engths greater than 50 ft horizontal,
or greater than 20 fl vertical differential,
consult the Application
Guideline
and Service Manual -- Air Conditioners
and Heat Pumps.
2 Do not apply capillary tube indoor coils to these units
OUTDOOR
E_IT
CONNE(TED
TO FACTORY
APPROVED
INDOOR
UNIT
Outdoor
unit contains
cmTect system
refrigerant
charge fbr opera-
tion with
indoor
unit of same
size when
connected
by 15 ft of
field-supplied
or f_cto_
accesso_
robing.
Check
rei'rigerant
charge
for maxin-mn_
efficiency.
REFRIGERANT
TUBING
Connect
robing
to fittings
on outdoor
unit
vapor-
and liquid-
service
valves.
(See Table
1.) Lse refi'igerant
grade
robing
SWEAT CONNE(TION
Remove
plastic
retainer
holding
outdoor
piston
in liquid
service
vah'e
and connect
sweat/flare
adapter
provided
to vah'e
(See Fig
7) Connect
refi'igerant
robing
to fittings
on outdoor
unit vapor-
and liquid-service
valves.
Selwice valves
are closed
fi'om facto_
and tea@
for brazing.
After
wrapping
service
valve
with
a wet
cloth, robing set can be brazed
to service
valve using either
silver
bearing
or non-silver
bearing
brazing
material.
Consult
local code
requirements.
Refi'igerant
tubing and indoor coil are now ready
for
leak testing.
This check
should include
all field and fi_cto_" joints.
PISTON
PISTON
PISTON
RETAINER
STRAINER
"_'_
SWEAT/FLARE
ADAPTER
A97512
Fig. 7--Liquid-Service
Valve
mMPORTANT:
(beck
to be certain
fuctory
tubing
on both indoor
and outdoor
unit has not shifted during
shipment.
Ensure
tubes are
not
robbing
against
each
other
or any
sheet
metal.
Pay
close
attention
to feeder
tubes, making
sure wire ties on f_eder tubes are
secure
and tight
Step
10--Nake
Electrical
Connections
To avoid personal
injmy or death, do not supply power to unit
with compressor
terminal
box cover removed.
Be sure field wiring
complies
with local and national
fire, safkty,
and electrical
codes,
and voltage
to system
is within
limits shown
on unit rating plate
( ontact tocal power
company
fbr convction
of
improper
voltage.
See unit rating
plate
fbr recommended
circuit-
protection
device.
NOTE:
Operation
of unit
on improper
line voltage
constitutes
abuse and could affkct unit reliability
See unit rating plate
Do not
install unit in system
where voltage
may fluctuate
above or below
pem_issible
limits.
NOTE:
Lse
copper
wire
only
between
disconnect
switch
and
unit
NOTE:
Install
branch
circuit
disconnect
of adequate
size
per
NE(
to handle unit stmling cun'ent
Locate
disconnect
within sight
from and readily
accessible
from unit, per Section
440-14
of NEC.
ROUTE
GROUND
AND
POWER
WIRES
Remove
access
panel to gain access
to unit wiring.
Extend
wires
from disconnect
through
power
wiring
hole provided
and into unit
control
box
The unit
cabinet
must
have
an uninterropted
or unbroken
ground
to minimize
personal
injury
if an electrical
fhult
should
occur.
The ground
may consist
of electrical
wire
or
metal
conduit
when
installed
in accordance
with
existing
electrical
codes
Failure to fbllow this warning
can result in an
electric
shock,
fire, or death
CONNE(T
GROUND
AND POWER
WIRES
Connect
ground
wire
to ground
connection
in control
box
for
safety
Connect
power
wiring
to contactor
as shown
in Fig
8.
(ONNE(T
(ONTROL
WIRING
Route
24v
control
wires
through
contloi
wiring
grommet
and
connect
leads
to
control
wiring.
See
Them_ostat
Installation
Instractions
for wiring
specific
unit combinations
(See Fig. 9)
Use No. 18 AWG color coded,
insulated
(35_>C mininmm)
wire. If
thermostat
is located
more
than
100 ft fi'om unit,
as measured
along the contlol
voltage
wires, use No. 16 AWG color coded wire
to avoid
excessive
voltage
&op
All wiring
must
be NEC
Class
1 and must
be separated
from
incoming
power
leads

Advertisement

loading

This manual is also suitable for:

38byg