Troubleshooting
Fault messages
(cont.)
Displayed fault
System characteristics
code
395
Burner in a fault state
396
Burner in a fault state
399
Burner in a fault state
400
Burner in a fault state
401
Burner in a fault state
402
Burner in a fault state
403
Burner in a fault state
404
Burner in a fault state
405
Burner in a fault state
406, 408, 410
Burner in a fault state
416
Burner locked out
84
Cause
IO electrode earth fault,
HBMU heat management
unit faulty.
HBMU heat management
unit faulty.
IO electrode earth fault,
HBMU heat management
unit faulty.
HBMU heat management
unit faulty.
IO electrode earth fault,
HBMU heat management
unit faulty
HBMU heat management
unit faulty
Ionisation electrode earth
fault, HBMU heat man-
agement unit faulty
HBMU heat management
unit faulty
Ionisation electrode earth
fault, HBMU heat man-
agement unit faulty
HBMU heat management
unit faulty
Flue gas temperature sen-
sor incorrectly positioned
Measures
Check ignition electrode for earth
fault. If the fault persists, replace
the HBMU heat management unit.
Reset the appliance.
Replace the HBMU heat manage-
ment unit: See chapter "Replacing
the HBMU heat management unit".
Reset the appliance.
Check IO electrode for earth fault.
If the fault persists, replace the
HBMU heat management unit: See
chapter "Replacing the HBMU heat
management unit".
Reset the appliance.
Replace the HBMU heat manage-
ment unit: See chapter "Replacing
the HBMU heat management unit".
Reset the appliance.
Check IO electrode for earth fault.
If the fault persists, replace the
HBMU heat management unit: See
chapter "Replacing the HBMU heat
management unit".
Reset the appliance.
Replace the HBMU heat manage-
ment unit: See chapter "Replacing
the HBMU heat management unit".
Reset the appliance.
Check IO electrode for earth fault.
If the fault persists, replace the
HBMU heat management unit: See
chapter "Replacing the HBMU heat
management unit".
Reset the appliance.
Replace the HBMU heat manage-
ment unit: See chapter "Replacing
the HBMU heat management unit".
Reset the appliance.
Check IO electrode for earth fault.
If the fault persists, replace the
HBMU heat management unit: See
chapter "Replacing the HBMU heat
management unit".
Reset the appliance.
Replace the HBMU heat manage-
ment unit: See chapter "Replacing
the HBMU heat management unit".
Reset the appliance.
Fit flue gas temperature sensor
correctly. See "Repairs".
Carry out mains reset after fault
has been remedied.