4. Recovered refrigerant must come from a
"contaminant-free" system. To decide whether the
system is contaminant free, consider:
Type(s) of previous failure(s)
Whether the system was cleaned, evacuated
and recharged properly following failure(s)
Whether the system has been contaminated
by this failure
Compressor motor burnouts and improper past
service prevent refrigerant re-use.
Refer to "Remote Condenser Model
Procedure" on page 110 to test for
contamination.
5. "Substitute" or "Alternative" Refrigerant
Must use only Koolaire-approved alternative
refrigerants.
Must follow Koolaire-published conversion
procedures.
106