<RBC-AWSU52-UL>
Displays the codes and data indicating the operating condition and temperature of each sensor on the indoor units,
outdoor units, and remote controllers.
Indoor service monitor list
Code No.
00
Room temperature (Use to control)
01
Room temperature (Remote controller)
02
Indoor suction air temperature (TA)
03
Indoor coil temperature (TCJ)
04
Indoor coil temperature (TC2)
05
Indoor coil temperature (TC1)
06
Indoor discharge air temperature (TF) **
07
Indoor fan motor number of revolutions**
08
Indoor PMV opening
F3
Filter sign time
Suction temperature of air to air heat
F9
exchanger (TSA) **
Outside air temperature (TOA) **
FA
* When the units are connected to a group, data of the header indoor unit only can be displayed.
** There is also a model which cannot be displayed.
• Refer to the service manual of an outdoor unit for "outdoor service monitor list".
Data name
Display format
- 53 -
1
In the "Field setting menu
[
] and [
] to select "Monitor function
and then press [
Press [
] and [
then check the data.
 In a group connection, after a selection in the unit
selection screen, move to the "Monitor function"
screen.
2
Press [
Return]
 Return to the "Field setting menu" screen.
Unit
Remote controller display example
×1
°F(°C)
°F(°C)
×1
×1
°F(°C)
×1
°F(°C)
×1
°F(°C)
×1
°F(°C)
×1
°F(°C)
×1
[0600] = 600rpm
rpm
×1/10
pls
[0150]=1500pls
×1
h
[2500] = 2500h
°F(°C)
×1
[0024] = 75.2°F(24°C)
°F(°C)
×1
screen, press
"
Set/Fix]
] to change the item code and
,
"