3.

INSTALLATION WORK

Correct initial installation location is important because it is diffi cult to move unit after it is
installed.
3. 1.

Selecting an installation location

Select installation locations that can properly support the weight of the indoor. Install
the units securely so that they do not topple or fall.
Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside.
It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
• Area fi lled with mineral oil or containing a large amount of splashed oil or steam,
such as a kitchen.
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as
sulfuric gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause
refrigerant leakage.
• Area that can cause combustible gas to leak, contains suspended carbon fi bers or
fl ammable dust, or volatile infl ammables such as paint thinner or gasoline.
If gas leaks and settles around the unit, it can cause a fi re.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or fl ammable gas.
Install the unit where drainage does not cause any trouble.
Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote
controller cable at least 40 in. (1 m) away from a television or radio receivers. The
purpose of this is to prevent TV reception interference or radio noise.
(Even if they are installed more than 40 in. (1 m) apart, you could still receive noise
under some signal conditions.)
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
Decide the mounting position with the customer as follows:
(1) Install the indoor unit on a place having a suffi cient strength so that it withstands
against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) A place from where the air can be distributed evenly throughout the room by the unit.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the connection pipe can be easily installed.
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibrations are not amplifi ed.
(9) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the fi lter can be removed.
3. 2.

Installation dimensions

The ceiling height as shown in the fi gure.
10-3/32 in. (256 mm) or more (AUUB 18/24)
11-23/32 in. (298 mm) or more (AUUB 30/36)
Strong and durable ceiling
9 ft. 10-1/8 in. (3,000 mm) or more
H : 5 ft. 10-7/8 in. (1,800 mm) or more
39-3/8 in. (1,000 mm) or more
En-3
WARNING
CAUTION
59-1/16 in. (1,500 mm) or more
Obstruction
Floor
H (The maximum height from fl oor to ceiling) [ft. (mm)]
Model name
AUUB 18/24
9.8
Standard mode
(3,000)
11.5
High Ceiling mode
(3,500)
Discharge Direction Setting
• The discharge direction can be selected as shown below.
4 DIRECTION
3 DIRECTION
*
Select the most appropriate airfl ow direction from 3 or 4 directions according to the
shape of the room and the installation position.
*
When changing the number of outlets, we recommend using the optional AIR OUT-
LET SHUTTER PLATE KIT to close the outlet.
*
For the specifi c closing pattern, please refer to the attached AIR OUTLET SHUTTER
PLATE KIT'S MANUAL. (Do so before installing the decorative panel as it will be
installed on the body.)
*
Be sure to make the function settings with the remote controller according to the
number of airfl ow outlets and the installed ceiling height.
AUUB 30/36
9.8
10.5
10.5
(3,000)
(3,200)
(3,200)
11.5
11.8
13.8
(3,500)
(3,600)
(4,200)
3-15/16 in.
(100 mm)
or more