Diagnosis and Adjustment (Error Code)
Error code related to the Communications / Settings / HW
Error mode
When number of MCU is not set correctly on the outdoor unit or when two or more MCU was installed some of
E-214
them have the same address
E-215
When two different MCU's have same address value on the rotary switch
E-216
When indoor unit is not installed to a MCU port but the switch on the port is set to On.
hen indoor unit is connected to a MCU port but indoor unit is assigned to a MCU and the switch
E-217
on the port is set to Off
When there's at least one or more actual number of indoor unit connection compared to number of indoor
E-218
units assigned to MCU
E-219
Error on temperature sensor located on MCU intercooler inlet (Short or Open)
E-220
Error on temperature sensor located on MCU intercooler outlet (Short or Open)
E-221
Error on outdoor temperature sensor of outdoor unit (Short or open)
E-224
Error on water temperature sensor of main outdoor unit (Short or Open)
E-225
Error on control box temperature sensor of main outdoor unit (Short or Open)
E-231
Error on COND OUT temperature sensor of main outdoor unit (Short or Open)
E-241
COND OUT sensor is detached
E-251
Error on discharge temperature sensor of compressor 1 (Short or Open)
E-257
Error on discharge temperature sensor of compressor 2 (Short or Open)
E-262
Discharge temperature sensor of compressor 1 is detached from the sensor holder on the pipe
E-263
Discharge temperature sensor of compressor 2 is detached from the sensor holder on the pipe
E-266
Top sensor of compressor 1 is detached
E-267
Top sensor of compressor 2 is detached
E-269
Suction temperature sensor is detached from the sensor holder on the pipe
E-276
Error on top sensor of compressor 1 (Short or Open)
E-277
Error on top sensor of compressor 2 (Short or Open)
E-291
Refrigerant leakage or error on high pressure sensor (Short or Open)
E-296
Refrigerant leakage or error on low pressure sensor (Short or Open)
E-308
Error on suction temperature sensor (Short or Open)
E-311
Error on temperature sensor of double layer pipe/liquid pipe(sub heat exchanger) (Short or Open)
E-321
Error on EVI (ESC) IN temperature sensor (Short or Open)
E-322
Error on EVI (ESC) OUT temperature sensor (Short or Open)
E-323
Error on suction sensor 2 (Short or Open)
E-346
Error due to operation failure of Fan2
E-347
Motor wire of Fan2 is not connected
E-348
Lock error on Fan2 of outdoor unit
E-353
Error due to overheated motor of outdoor unit's Fan2
E-355
Error due to overheated IPM of Fan2
E-361
Error due to operation failure of inverter compressor 2
E-364
Error due to over-current of inverter compressor 2
E-365
V-limit error of inverter compressor 2
E-366
Error due to over voltage /low voltage of inverter PBA2
E-367
Error due to unconnected wire of compressor 2
E-368
Output current sensor error of inverter PBA2
E-369
DC voltage sensor error of inverter PBA2
E-371
Error due to the INV2 Data Flash
Samsung Electronics
(cont.)
Cause
Troubleshooting
4-11