FFE FDL242 User Manual page 25

Linear smoke detector
Table of Contents

Advertisement

Line Separator
Line voltage:
Nominal
Minimum
Maximum
Voltage at which the line separator opens:
Minimum
Maximum
Permanent current when switches are closed
Switching current
(e.g., in the event of a short-circuit)
Leakage current when switches are open
Serial impedance when switches are closed
The line separator is closed via an actuation signal from the control panel. Required line voltage:
DC 32 V (= V
)
nom
DC 12 V (= V
)
min
DC 33 V (= V
)
max
DC 7.5 V (= V
)
SO min
DC 10.5 V (= V
)
SO max
Max. 1.5 A (= I
)
C max
Max. 2 A (= I
)
S max
Max. 1 mA (= I
)
L max
Max. 0.4 Ω (= Z
)
C max
DC 12...33 V (normal range)