Carrier WeatherMaster 50HC14 Installation Instructions Manual page 18

Single package rooftop cooling only unit with puron (r-410a) refrigerant
Table of Contents

Advertisement

Pwd-CO
Fuse
Switch
Convenience
Outlet
GFCI
Disconnect
Access Panel
Fig. 29 — Convenience Outlet Location
Unit-powered type: A unit-mounted transformer is facto-
ry-installed to stepdown the main power suppl voltage to the
unit to 115-v at the duplex receptacle. This option also includes
a manual switch with fuse, located in a utility box and mounted
on a bracket behind the convenience outlet; access is through
the unit's control box access panel. See Fig. 29.
The primary leads to the convenience outlet transformer are
not factory-connected. Selection of primary power source is a
customer-option. If local codes permit, the transformer primary
leads can be connected at the line-side terminals on the unit-
mounted non-fused disconnect; this will provide service power
to the unit when the unit disconnect switch is open. Other con-
nection methods will result in the convenience outlet circuit be-
ing de-energized when the unit disconnect switch is open. See
Fig. 31. On a unit without a unit-mounted disconnect, connect
the source leads to the main terminal block (TB1).
If the convenience outlet transformer is connected to the
line side of a field disconnect, the conduit provided with the
unit must be used to protect the wire as they are routed from the
transformer to the field disconnect. The end of the conduit with
the straight connector attaches to the field disconnect. The oth-
er end does not need to connect to the transformer; however,
the conduit must be routed so that all wiring is either in the con-
duit or behind the access panel.
If the convenience outlet transformer is connected to the
line side of the factory disconnect option, route the wires
through the web bushing located on the bottom of the discon-
nect box. For the load side wiring to the factory option discon-
nect, route the wires through the hole on the right side of the
disconnect. Be sure to create a drip loop at least 6-in. long.
Test the GFCI receptacle by pressing the TEST button on
the face of the receptacle to trip and open the receptacle. Check
for proper grounding wires and power line phasing if the GFCI
receptacle does not trip as required. Press the RESET button to
clear the tripped condition.
Pwd-CO
Transformer
VOLTAGE
Fig. 31 — Unit Powered Convenience Outlet Wiring
tron" T-15, non-renewable screw-in (Edison base) type plug
fuse.
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Using unit-mounted convenience outlets: Units with unit-
mounted convenience outlet circuits will often require that
two disconnects be opened to de-energize all power to the
unit. Treat all units as electrically energized until the con-
venience outlet power is also checked and de-energization
is confirmed. Observe National Electrical Code Article
210, Branch Circuits, for use of convenience outlets.
use cover for the factory-installed convenience outlets is now
required by UL standards. This cover cannot be factory-mount-
18
NOTICE/AVIS
Convenience Outlet Utilization
Maximum Intermittent Use 15 - Amps
Maximum Continuous Use 8 - Amps
Observe a 50% limit on the circuit
Loading above 8 - Amps
Utilisation de la prise utilitaire
Usage intermittent maximum 15 - Amps
Usage continu maximum 8 - Amps
Observez une limite de 50% sur le circuit
Chargement au-dessus de 8 - Amps
Fig. 30 — Convenience Utilization Notice
UNIT
CONNECT
PRIMARY
AS
CONNECTIONS
L1: RED +YEL
208,230
240
L2: BLU + GRA
L1: RED
460
480
Splice BLU + YEL
L2: GRA
L1: RED
575
600
L2: GRA
Fuse on power type: The factory fuse is a Bussman "Fuse-
WARNING
Installing Weatherproof Cover: A weatherproof while-in-
50HE501288
2.0
TRANSFORMER
TERMINALS
H1 + H3
H2 + H4
H1
H2 + H3
H4
H1
H2

Advertisement

Table of Contents
loading

Table of Contents