Ductwork; Side Panels; Side Panels With Hole Plugs; Return Downflow Plenum With Panel - York ZKT06 Installation Manual

Table of Contents

Advertisement

Ductwork

You must design and size ductwork according to the methods in
Manual D of the Air Conditioning Contractors of America
(ACCA) or as recommended by any other recognized authority
such as ASHRAE or SMACNA. When you design the duct
system, apply the following recommendations.
• Use a closed return duct system. This does not preclude
the use of economizers or outdoor fresh air intake.
• Make the supply and return air duct connections at the
unit with flexible joints to minimize noise.
• Design the supply and return air duct systems for the CFM
and static pressure requirements of the job. Do not size
them to match the dimensions of the duct connections on
the unit.
See Figure 10 for bottom air duct openings. See Figures 12 and
13, and Table 7 for side air duct openings.
Duct covers
Units are shipped with the side duct openings covered.
For a bottom duct application, no duct cover changes are
necessary.
For a side duct application, complete the following steps.
1.
Remove the side duct covers.
2.
Orient the supply panel with the painted surface up.
3.
Slide the supply panel between the heat exchanger and
the unit bottom. The painted surface must face the heat
exchanger. The space is narrow but there is adequate
room to install the panel.
4.
Secure the supply panel with the factory-installed bracket
and two screws.
5.
Orient the return panel with the painted surface down.
6.
Install the return panel over the corresponding side duct.
the painted surface must face the down flow duct opening.
7.
Secure the return panel with four screws.
When you fasten ductwork to the side duct flanges on
the unit, insert the screws through duct flanges only. DO
NOT insert the screws through the casing. You must
insulate and water-proof outdoor ductwork.
Johnson Controls Ducted Systems
Figure 17: Side panels with hole plugs
Note: Note the orientation of the panel with the insulation side
facing up.
Figure 18: Return downflow plenum with panel
Figure 19: Discharge panel in place

Side panels

Units are shipped with side panels to cover the area where an
economizer or motorized damper may be installed. You must
keep these panels to use them as tops for the economizer rain
hoods (see Figure 20).
5121835-TIM-J-1118
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zk seriesZkt07Zkt08Zkt10Zkt12

Table of Contents