Table 2.A
Wire/Terminal Connections for Imtermediate Nodes
For this Wire/Pair
Connect this Wire
Shield/Drain
Non jacketed
Black/White
Black Wire
White Wire
Black/Red
Black Wire
Red Wire
The nodes at each end of the network must be terminated. Install a jumper
wire between terminals 5 and 6 to enable the impedance built into the
module.
One (not both) of the nodes at the end of the network must have an earth
ground connection for the communication cable shield. For the node
at one end of the network, whether it is the KF3 or some other device,
connect the shield to ground by installing a jumper wire between terminals
1 and 2 of the terminal block.
CAUTION: Be sure no other node on the network has its shield
connected to ground.
Figure 2.3 illustrates proper jumper connections for end nodes.
Figure 2.3
Jumper Connections for End Nodes
Jumper to
ground shield
KF3 on one end of the link
* The black wire of the white/black pair should be cut back (no connection).
Chapter 2
Installing the KF3
To this Terminal
Terminal 2 - Shield
Cut back - No connection
Terminal 3 (Signal Ground)
Terminal 4 (Data A)
Terminal 5 (Data B)
Jumper to
terminate node
Jumper to
terminate node
SLC 500 or other device on the other
end of the link