IX. HYDRONIC PIPING (CONTINUED)
D. Temperature Rise and Heat Exchanger Head Loss
1. The PFC heat exchanger adds pressure drop to the system which must be accounted for in the design of the
piping configuration and pump selection.
2. For systems with glycol mixture, the flow rate specified in Table 21 will increase as specified in Table 25 due
to the extra frictional loss introduced by the glycol. Size pump accordingly.
3. Strictly follow glycol manufacturer's guidelines and recommendations when adding glycol in the heating system.
4. The system should be designed to maintain the recommended water flow rate shown in Table 21 while never
exceeding the range of absolute flow rates shown in Table 24. Exceeding the maximum water flow rates can
cause pipe erosion, damage the flow switch, and allow unsafe operation.
a. Maintaining sufficient flow through the boiler will help prevent the buildup of scale.
Table 21: Temperature rise, flow rate, and head loss
Recommended Range
Delta 20 °F
Delta 25 °F
PFC
Head
Boiler
GPM
Loss
GPM
Model
(ft)
2000
194
19.7
155
2500
242
15.4
194
3000
291
20
232
3500
339
14.4
271
4000
388
18.1
310
Required Flow = Output×1000/(500×ΔT), where flow rate is in GPM, output is in MBH, and ΔT is in 0F, Outputs are
shown in Table 1.
This Boiler has a temperature rise limit of 55 °F
20
16.7
13.35
10
6.7
3.35
38
Delta 30 °F
Head
Head
Loss
GPM
Loss
(ft)
(ft)
13.9
129
10.5
11.3
161
8.9
14.6
194
11.3
10.0
226
7.6
12.4
258
9.3
0
50
100
Figure 13: Heat exchanger water pressure loss
Delta 35 °F
Delta 40 °F
Head
Head
GPM
Loss
GPM
Loss
(ft)
(ft)
111
8.2
97
6.7
138
7.2
121
6.1
166
9.2
145
7.7
194
6.1
170
5.2
221
7.4
194
6.1
150
200
250
Water Flow Rate (gal/min)
Delta 45 °F
Delta 50 °F
Head
Head
GPM
Loss
GPM
Loss
(ft)
(ft)
86
5.6
80
4.7
107
5.2
97
4.6
129
6.6
116
5.8
150
4.5
135
4.0
172
5.3
155
4.7
1250 MBtu/h
1500 MBtu/h
2000 MBtu/h
3000 MBtu/h
4000 MBtu/h
300
350
400
PFC2000-4000 Boiler I,O&M Manual Rev. 2
Delta 55 °F
Head
GPM
Loss
(ft)
71
4.1
88
4.0
105
5.1
123
3.7
141
4.2