Anti-Freezing Option 1
This function is to select whether to use Type1 or Type2 to prevent freezing when the remote
control is turned off.
• Change setting values using [<,>(left/right)] button.
CAUTION
!
If the function is set to Type 2, there is a risk of freezing.
Function
Detection
Type 2 + Inlet
Type 1
Temp.
Type 2
Air Temp.
Value
Type1(Default)
Case
Air Temp. < Certain Level
Inlet Temp. < Certain Level
Air Temp. < Certain Level
Inlet Temp. > Certain Level
Air Temp. > Certain Level
Inlet Temp. > Certain Level
Air Temp. < Certain Level
Air Temp. > Certain Level
INSTALLER SETTING
Type2
Operation
Pump always ON
Pump intermittently On
Pump always OFF
Pump intermittently On
Pump always OFF
133