2)
Capacitor Reconditioning procedure
If the leakage current is over 5mA,
apply DC voltage to 400V gradually.
,-1....---,
After the capacitor has been changed
for 30 " 60 min. the capacitor is
reconditioned .
v.riahle volt&ge
power
."'~rc.
3)
Storage of Loose Capacitors
The capacitor should be stored in a cool and dark place if possible.
Higher temperatures deteriorate the characteristics faster. Sunlight
may cause discoloration of the sleeve as well as deterioration of
sealing rubber. High humidity may cause solderability problems
on the terminals.