VAV Zone Controller
32-122 °F (0-50 °C) Non-condensing
REV 5.0 / PL-QCK-WSENSOR/VC2000-EN
(PL-VC2000)
Network communication
General purpose analog input
(0-5 VDC, 4-20mA, 10K thermistor)
Supply / Radiant / Zone / Occupancy / Discharge
Digital Sensor (T1000, T500 or T200) /
Remote computer with Focus
Analog Output: Demand, Duct Heater, Fan Powered Box
Series or Parallel, Radiant Floor, Slave Damper, Occupancy,
Baseboard, Zone Valve
Digital Output: Demand, Duct Heater, Fan Powered Box
Series or Parallel, Radiant Floor, Occupancy, Baseboard,
Zone Valve
Power source of the controller
(24 VAC - Class 2)
Service pin
Airflow Sensor (PL-VC2000-PI)
Airflow sensors are only included in the PL-VC2000-PI
models only. Adding an airflow sensor to the Prolon VC2000
lets it regulate the airflow as well as temperature in a zone,
independently of the static pressure variations of the system.
The default flow sensor has a range of 0 to 2 in H20
(0 to 500 Pa). Depending on the flow cross used, this
translates to roughly 0-3500 ft/min.
cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1