Download Print this page

Viking VK697 Technical Data Manual page 4

Attic upright specific application sprinkler

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Part
Maximum
SIN
Number
Pressure
1
21716
VK697
175 psi
Approved Temperature Rating
A - 200 °F (93.3 °C)
1
Also refer to Viking's current price schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
3
This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
4
Listed by Underwriters Laboratories Inc. for use in the United States and Canada.
5
cULus Listed as corrosion resistant.
6
Refer to Design Criteria.
Allowable Roof Span, Flow, Pressure and Slope for Specific Application Sprinkler Protecting Attics
Thread Size
Sprinkler
Base Part
SIN
Number
NPT
21716
VK697
1/2"
1
Pitch and slope indicate the incline of a roof, expressed as a proportion of the vertical rise to the horizontal run.
2
The Attic Upright spacing when measured perpendicular to the slope is maximum 10 ft. (3,1 m) or when measured parallel to the slope is
maximum 12 ft. (3,6 m).
3
The VK697 is approved in 2.5:12 to 6:12 roof pitches when used with the VK690.
4
The VK697 is approved in 4:12 to 12:12 roof pitches in all other attic applications.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form F_080614 for
general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edi-
tion of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also
with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F_042517
Rev 01
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
APPROVAL CHART
Attic Upright Specific Application Sprinkler VK697
For Combustible and Non-Combustible Sloped Attic Spaces
Thread Size
NPT
BSP
U.S.
1/2"
15 mm
5.6
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1)
Nominal
K-Factor
BSP
U.S.
metric
15 mm
5.6
80
10 (3,1) x 12 (3,6)
February 2023
Nominal
Overall Length
K-Factor
metric
Inches
mm
2
80
2-1/4
57
Footnotes
Minimum
Allowable Roof
Flow
Span
2
Ft. (M)
GPM
LPM
Minimum 7 psi (0,48 Bar)
Minimum 0.10 gpm/ft
(4,1 mm/min.) Design Density
Footnotes
ATTIC UPRIGHT
SPECIFIC APPLICATION
SPRINKLER VK697
Listings and Approvals
cULus
3, 4, 6
A1, A2
Approved Finish
1 - Brass, 2 - ENT
5
Minimum
Dry Pipe System
Pressure
Maximum Water
Pitch
1, 3, 4
PSI
BAR
2.5:12 to
2
12:12
(All System Sizes)
Page 4 of 9
Delivery Time
(in seconds)
60 seconds