Viking VK5141 Technical Data Manual
Viking VK5141 Technical Data Manual

Viking VK5141 Technical Data Manual

Specific application esfr pendent sprinkler

Advertisement

Quick Links

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1.
DESCRIPTION
Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK5141 is a
fast response glass bulb type sprinkler designed for use in storage areas prone
to high-challenge fires. With a 28.0 (404 metric) nominal K-Factor and special
deflector, this sprinkler produces large, high-momentum water droplets in a
hemispheric pattern below the deflector. This permits penetration of the fire plume
and direct wetting of the burning fuel surface while cooling the atmosphere early
in the development of a high-challenge fire.
Refer the Approval Chart and Design Criteria Listing requirements that must be
followed.
2.
LISTINGS AND APPROVALS
UL Listed: Category VNWH (Listed as a Specific Application ESFR
Sprinkler)
3.
TECHNICAL DATA
Specifications:
Available since 2024
Maximum Working Pressure: 175 psi (12 bar).
Factory tested pneumatically to 95 psi (6.55 bar)
Thread size: 1" NPT or 25 mm BSPT
Nominal K-Factor: 28.0 U.S. (404 metric*)
* Metric K-factor measurement shown is in bar. When pressure is measured in kPa,
divide the metric K-factor shown by 10.0.
Overall Length: 3-1/4" (83 mm)
Deflector Diameter: 1-3/4" (45 mm)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Material Standards:
Frame: Brass CW602N
Deflector: Phosphor Bronze UNS-C51000
Pip cap and Insert assembly: Copper UNS-C11000, Stainless Steel UNS-
S30400 and UNS-S31600
Belleville Spring Sealing Assembly: Nickel Beryllium, coated on both
sides with PTFE Tape
Compression Screw: Brass, UNS-C36000
Bulb: Glass, Nominal 3mm diameter
Frame
Glass bulb
Deflector
Figure 1: Sprinkler Components
Form No. F_080622
Rev 03
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Belleville Spring
Sealing Assemby
(internal)
Pip cap and insert
assembly
Compression
Screw
January 2024
SPECIFIC APPLICATION
ESFR PENDENT
SPRINKLER VK5141 (K28.0)
SPRINKLER GENERAL INFORMATION
Item
Sprinkler Identification
Number (SIN)
K-factor, gpm/psi
Thread Size
Sprinkler Orientation
Maximum Working Pressure
PSI (bar)
17/8"
(48 mm)
13/8"
(35 mm)
Dimensions are
approximate.
Figure 2: Sprinkler Dimensions
Replaces Form No. F_080622 Rev 02
(Revised part numbers and images)
Page 1 of 6
TABLE 1
Description
VK5141
(lpm/bar
)
28.0 (404)
½
½
1" NPT
25 mm BSPT
Pendent
175 psi (12 bar)
1³/4"
(45 mm)

Advertisement

loading
Need help?

Need help?

Do you have a question about the VK5141 and is the answer not in the manual?

Questions and answers

Summary of Contents for Viking VK5141

  • Page 1 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK5141 is a fast response glass bulb type sprinkler designed for use in storage areas prone to high-challenge fires.
  • Page 2: Technical Data

    Add the suffix for the desired temperature rating. EXAMPLE: 25247AB = VK5141 with brass finish and 155 °F (68 °C) nominal temperature rating. This sprinkler is to be installed into an area with a maximum ambient temperature of 100 °F (38 °C).
  • Page 3: Installation

    INSTALLATION WARNINGS Viking sprinklers are manufactured and tested to meet rigid requirements of the approving agencies. The sprinklers are designed to be installed in accordance with recognized installation standards. System design must be based on ESFR design guidelines described in the latest edition of NFPA Standards, the Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards when- ever applicable.
  • Page 4: Operation

    Installation standards require sprinklers to be tested and, if necessary, replaced after a specified term of service. For Viking ESFR Pendent Sprinklers, refer to the Installation Standards (e.g., NFPA 25) and the Authorities Having Jurisdiction for the specified period of time after which testing and/or replacement is required. Sprinklers that have operated cannot be reassembled or reused, but must be replaced.
  • Page 5 IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Viking ESFR Pendent Sprinklers are to be installed in accordance with the latest edition of Viking technical data, the latest standards of NFPA, VdS, LPCB, and any other Authorities Having Jurisdiction, and also with provisions of governmental codes, ordinances, and standards whenever applicable.
  • Page 6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 4: COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FOR MODEL VK5141...
  • Page 7 1. DESCRIPTION Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An open sprinkler does not use an operating element and is open at all times.
  • Page 8 TECHNICAL DATA SPRINKLER OVERVIEW The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow arrow in the direction of discharge.
  • Page 9 Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
  • Page 10 Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com.
  • Page 11 * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com.
  • Page 12 • while ceiling finish work is being completed. Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is • temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
  • Page 13 Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after •...
  • Page 14 Viking ESFR Upright Sprinklers: Use Viking Wrench Part Number 05118CW/B. • Viking ESFR Pendent K14 and K16.8 Sprinklers: Use Viking Wrench Part Number 10285W/B or double-ended 13635W/B (Side A). • Viking ESFR Pendent K25.2 Sprinklers: Use Viking Wrench Part Number 12143W/B or double-ended 13635W/B (Side B).
  • Page 15: Warranty Terms And Conditions

    For more information, go to www.P65Warnings.ca.gov 2. WARRANTY TERMS AND CONDITIONS For details of warranty, refer to Viking’s current list price schedule at www.vikinggroupinc.com or contact Viking directly. New Bulletin Form No. F_111218 18.11.15...