Mitsubishi Electric MSZ-GS09NA Installation Manual page 6

Hide thumbs Also See for MSZ-GS09NA:
Table of Contents

Advertisement

3. Outdoor Unit Installation
3. Outdoor Unit Installation
3-1. Connecting Wires for the Outdoor Unit
3-1. Connecting Wires for the Outdoor Unit
1) Remove the service panel.
1) Remove the service panel.
2) Remove the conduit cover.
2) Remove the conduit cover.
3) Attach the conduit connectors to the conduit plate with lock nuts then secure it against unit with
3) Attach the conduit connectors to the conduit plate with lock nuts then secure it against unit with
screws.
screws.
4) Connect the ground wires of indoor/outdoor unit connecting wire (A) and power supply cord (K)
4) Connect the ground wires of indoor/outdoor unit connecting wire (A) and power supply cord (K)
to the TB support.
to the TB support.
5) Loosen the terminal screws, then attach indoor/outdoor unit connecting wire (A) and power sup-
5) Loosen the terminal screws, then attach indoor/outdoor unit connecting wire (A) and power sup-
ply cord (K) from the indoor unit correctly to the terminal block. Attach the wires to the terminal
ply cord (K) from the indoor unit correctly to the terminal block. Attach the wires to the terminal
block securely so that the cores cannot be seen, and no external force affects the connecting
block securely so that the cores cannot be seen, and no external force affects the connecting
section of the terminal block.
section of the terminal block.
6) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fastened.
6) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fastened.
7) Install the conduit cover.
7) Install the conduit cover.
8) Install the service panel securely.
8) Install the service panel securely.
Service panel
Service panel
3-2. Flare Connection
3-2. Flare Connection
1) Cut the copper pipe as straight as possible with a pipe cutter. (Fig. 1, 2)
1) Cut the copper pipe as straight as possible with a pipe cutter. (Fig. 1, 2)
2) Remove all burrs from the cut section of the pipe, ensuring that precautions are taken to
2) Remove all burrs from the cut section of the pipe, ensuring that precautions are taken to
avoid getting metal shavings into the piping. (Fig. 3)
avoid getting metal shavings into the piping. (Fig. 3)
3) Remove flare nuts attached to indoor and outdoor units, then put them on pipe.
3) Remove flare nuts attached to indoor and outdoor units, then put them on pipe.
4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in the table. Select
4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in the table. Select
A inch (mm) from the table according to the tool you use.
A inch (mm) from the table according to the tool you use.
5) Check
5) Check
• Compare the flared work with Fig. 6.
• Compare the flared work with Fig. 6.
• If flare is defective, cut off the section and repeat procedure.
• If flare is defective, cut off the section and repeat procedure.
Pipe diam-
Pipe diam-
B
B
Clutch
Clutch
eter inch
eter inch
inch
inch
type tool
type tool
(mm)
(mm)
(mm)
(mm)
for R410A
for R410A
21/32
21/32
ø 1/4 (6.35)
ø 1/4 (6.35)
(17)
(17)
7/8
7/8
ø 3/8 (9.52)
ø 3/8 (9.52)
(22)
(22)
0 to 0.02
0 to 0.02
(0 to 0.5)
(0 to 0.5)
1-1/32
1-1/32
ø 1/2 (12.7)
ø 1/2 (12.7)
(26)
(26)
1-5/32
1-5/32
ø 5/8 (15.88)
ø 5/8 (15.88)
(29)
(29)
3-3. Pipe Connection
3-3. Pipe Connection
• Fasten flare nut with a torque wrench as specified in the table (refer to 3-2.).
• Fasten flare nut with a torque wrench as specified in the table (refer to 3-2.).
• When fastened too tight, flare nut may eventually break and cause refrigerant leakage.
• When fastened too tight, flare nut may eventually break and cause refrigerant leakage.
• Be sure to wrap insulation around the piping. Direct contact with the bare piping may result
• Be sure to wrap insulation around the piping. Direct contact with the bare piping may result
in burns or frostbite.
in burns or frostbite.
Indoor unit connection
Indoor unit connection
Connect both liquid and gas pipings to indoor unit.
Connect both liquid and gas pipings to indoor unit.
• Do not apply refrigeration oil on screw threads. Excessive tightening torque will result in
• Do not apply refrigeration oil on screw threads. Excessive tightening torque will result in
damage on the screw.
damage on the screw.
• To connect, first align the center, then tighten the first 3 to 4 turns of flare nut by hand.
• To connect, first align the center, then tighten the first 3 to 4 turns of flare nut by hand.
• Use tightening torque table above as a guideline for indoor unit side joints, and tighten
• Use tightening torque table above as a guideline for indoor unit side joints, and tighten
using two wrenches. Excessive tightening damages the flare section.
using two wrenches. Excessive tightening damages the flare section.
Outdoor unit connection
Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit following the same procedure
Connect pipes to stop valve pipe joint of the outdoor unit following the same procedure
detailed in Indoor unit connection.
detailed in Indoor unit connection.
• For tightening, use a torque wrench or spanner.
• For tightening, use a torque wrench or spanner.
When installing the unit, securely connect the refrigerant pipes before starting
When installing the unit, securely connect the refrigerant pipes before starting
the compressor.
the compressor.
3-4. Insulation and Taping
3-4. Insulation and Taping
1) Cover piping joints with pipe cover.
1) Cover piping joints with pipe cover.
2) For outdoor unit side, insulate the piping, including valves.
2) For outdoor unit side, insulate the piping, including valves.
3) Apply piping tape (G) starting from the connection on the outdoor unit.
3) Apply piping tape (G) starting from the connection on the outdoor unit.
• When piping has to be installed through a ceiling, closet or where the temperature and
• When piping has to be installed through a ceiling, closet or where the temperature and
humidity are high, use additional field-supplied insulation to prevent condensation.
humidity are high, use additional field-supplied insulation to prevent condensation.
Lock nut
Lock nut
Conduit cover
Conduit cover
A inch (mm)
A inch (mm)
Tightening torque
Tightening torque
Clutch
Clutch
Wing nut
Wing nut
ft-lb
ft-lb
type tool
type tool
type tool
type tool
(kgf•cm)
(kgf•cm)
for R22
for R22
for R22
for R22
10 to 13
10 to 13
0.06 to
0.06 to
(140 to 180)
(140 to 180)
0.08
0.08
(1.5 to
(1.5 to
25 to 30
25 to 30
0.04 to
0.04 to
2.0)
2.0)
(350 to 420)
(350 to 420)
0.06
0.06
(1.0 to
(1.0 to
36 to 42
36 to 42
0.08 to
0.08 to
1.5)
1.5)
(500 to 575)
(500 to 575)
0.10
0.10
(2.0 to
(2.0 to
54 to 58
54 to 58
2.5)
2.5)
(750 to 800)
(750 to 800)
Warning
Warning
Lead wire
Lead wire
Terminal block
Terminal block
Conduit plate
Conduit plate
Conduit pipe
Conduit pipe
TB support
TB support
to conduit cover
to conduit cover
N•m
N•m
13.7 to 17.7
13.7 to 17.7
34.3 to 41.2
34.3 to 41.2
49.0 to 56.4
49.0 to 56.4
73.5 to 78.4
73.5 to 78.4
Indoor unit
Indoor unit
connection
connection
Outdoor unit
Outdoor unit
connection
connection
19/32 inch
19/32 inch
(15 mm)
(15 mm)
• Make earth wire a little longer than others.
• Make earth wire a little longer than others.
(More than 3-7/8 inches [100 mm])
(More than 3-7/8 inches [100 mm])
• For future servicing, leave some slack in the
• For future servicing, leave some slack in the
connecting wires.
connecting wires.
Grounding
Grounding
terminal
terminal
Indoor/outdoor unit
Indoor/outdoor unit
connecting wire (A)
connecting wire (A)
Power supply cord (K)
Power supply cord (K)
90°
90°
Copper
Copper
pipe
pipe
Fig. 1
Fig. 1
Copper pipe
Copper pipe
Burr
Burr
Spare reamer
Spare reamer
Pipe cutter
Pipe cutter
Flaring tool
Flaring tool
Die
Die
Flare nut
Flare nut
Clutch type
Clutch type
Wing nut type
Wing nut type
Fig. 4
Fig. 4
Smooth all around
Smooth all around
Inside is shining without any scratches.
Inside is shining without any scratches.
Even length all around
Even length all around
Flare nut
Flare nut
Internal thread side
Internal thread side
Tighten the flare nut
Tighten the flare nut
with a torque wrench.
with a torque wrench.
L1 L2
L1 L2
Power supply cord (K)
Power supply cord (K)
Good
Good
No good
No good
Tilted
Tilted
Uneven Burred
Uneven Burred
Fig. 2
Fig. 2
Fig. 3
Fig. 3
Copper pipe
Copper pipe
Fig. 5
Fig. 5
Fig. 6
Fig. 6
Union joint
Union joint
External thread side
External thread side
Grip the nut on the
Grip the nut on the
union joint with a spanner.
union joint with a spanner.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents