N80MSN/N80MSL: Installation, Start–Up, Operating and Service and Maintenance Instructions
2. Firmly touch the clean, unpainted, metal surface of the furnace
chassis which is close to the control. Firmly touch the clean,
unpainted, metal surface of the furnace chassis which is close to the
control. Tools held in a person's hand during grounding will be
satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control
or connecting wires as long as you do nothing to recharge your
body with static electricity (for example; DO NOT move or shuffle
your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with
static electricity), firmly touch a clean, unpainted metal surface of
the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded)
furnaces.
6. Before removing a new control from its container, discharge your
body's electrostatic charge to ground to protect the control from
damage. If the control is to be installed in a furnace, follow items 1
through 4 before bringing the control or yourself in contact with the
furnace. Put all used and new controls into containers before
touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also
be used to prevent ESD damage.

LOCATION

GENERAL
This multipoise furnace is shipped in packaged configuration. Some
assembly and modifications are required when used in any of the four
applications (see
Fig.
3).
This furnace must:
• be installed so the electrical components are protected from water.
• not be installed directly on any combustible material other than wood
flooring for upflow applications. Downflow installations require use
of a factory-approved floor base or coil assembly when installed on
combustible materials or wood flooring (refer to SAFETY
CONSIDERATIONS).
• be located as close to the chimney or vent and attached to an air
distribution system. Refer to Air Ducts section.
• be provided ample space for servicing and cleaning. Always comply
with minimum fire protection clearances shown on the furnace
clearance to combustible label.
The following types of furnace installations may require OUTDOOR
AIR for combustion due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Laundry rooms
• Hobby or craft rooms, and
• Chemical storage areas
If air is exposed to the following substances, it should not be used for
combustion air, and outdoor air may be required for combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
• Masonry acid washing materials
All fuel-burning equipment must be supplied with air for fuel
combustion. Sufficient air must be provided to avoid negative pressure
in the equipment room or space. A positive seal must be made between
the furnace cabinet and the return-air duct to prevent pulling air from the
burner area and from draft safeguard opening.
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream
side of the unit to avoid condensation in the heat exchangers. When
installed parallel with the furnace, dampers or other flow control must
prevent chilled air from entering the furnace. If the dampers are
manually operated, they must be equipped with means to prevent
operation of either unit unless the damper is in the full-heat or full-cool
position.
!
PERSONAL INJURY AND/OR PROPERTY DAMAGE
HAZARD
Improper use or installation of this furnace may cause premature
furnace component failure.
This gas furnace may be used for heating buildings under construction
provided that:
-
The furnace is permanently installed with all electrical wiring,
piping, venting and ducting installed according to these
installation instructions. A return air duct is provided, sealed to
the furnace casing, and terminated outside the space containing
the furnace. This prevents a negative pressure condition as
created by the circulating air blower, causing a flame rollout
and/or drawing combustion products into the structure.
-
The furnace is controlled by a thermostat. It may not be "hot
wired" to provide heat continuously to the structure without
thermostatic control.
-
Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other
construction materials. It also prevents the entrainment of
drywall dust into combustion air, which can cause fouling and
plugging of furnace components.
-
The temperature of the return air to the furnace is maintained
between 55°F (13°C) and 80°F (27°C), with no evening setback
or shutdown. The use of the furnace while the structure is under
construction is deemed to be intermittent operation per our
installation instructions.
-
The air temperature rise is within the rated rise range on the
furnace rating plate, and the gas input rate has been set to the
nameplate value.
-
The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
-
The furnace, ductwork and filters are cleaned as necessary to
remove drywall dust and construction debris from all HVAC
system components after construction is completed.
-
Verify proper furnace operating conditions including ignition,
gas input rate, air temperature rise, and venting according to
these installation instructions.