Gallagher
T10 Reader
Installation Note
T10 Mifare Reader Black: C300400
T10 Mifare Reader White: C300401
T10 PIV Reader Black: C305400
T10 PIV Reader White: C305401
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
Page 1

Advertisement

Table of Contents
loading

Summary of Contents for Gallagher C300400

  • Page 1 T10 Reader Installation Note T10 Mifare Reader Black: C300400 T10 Mifare Reader White: C300401 T10 PIV Reader Black: C305400 T10 PIV Reader White: C305401 3E4288 Gallagher T10 Reader | Edition 1 | August 2016 Copyright © Gallagher Group Limited Page 1...
  • Page 2 Although every commercially reasonable effort has been taken to ensure the quality and accuracy of the information, Gallagher Group makes no representation as to its accuracy or completeness and it should not be relied on as such. To the extent permitted by law, all express or implied, or other representations or warranties in relation to the information are expressly excluded.
  • Page 3: Table Of Contents

    Installation ............................7 LED indications ..........................9 Accessories ............................ 10 Technical specifications ........................10 Approvals and standards ........................ 11 Mounting dimensions ........................12 3E4288 Gallagher T10 Reader | Edition 1 | August 2016 Copyright © Gallagher Group Limited Page 3...
  • Page 4: Introduction

    Introduction The Gallagher T10 Reader is a smart card proximity reader. It can be installed as either an entry reader or exit reader. The reader sends information to the Gallagher Controller and acts upon information sent from the Gallagher Controller. The reader itself does not make any access decisions.
  • Page 5 2.3 Cabling The Gallagher T10 Reader requires a minimum cable size of 4 core 24 AWG (0.2 mm ) stranded security cable. This cable allows the transmission of data (2 wires) and power (2 wires). When using a single cable to carry both power supply and data, both the power supply voltage drop and data requirements must be considered.
  • Page 6 9 Vdc to function correctly. The cable length and the number of readers connected will have an impact on the voltage at each reader. 3E4288 Gallagher T10 Reader | Edition 1 | August 2016 Copyright © Gallagher Group Limited...
  • Page 7: Distance Between Readers

    Ensure both you and the equipment are earthed before beginning any servicing. The Gallagher T10 Reader is designed to be mounted on any solid flat surface. However installation on metal surfaces, particularly those with a large surface area will reduce read range. The extent to which the range is reduced will depend upon the type of metal surface.
  • Page 8 HBUS Reader or a Cardax IV Reader, as shown. Note: Gallagher PIV readers must be connected as HBUS Readers. Gallagher PIV readers connect to the Gallagher Controller 6000 High Spec PIV (C305101) only.
  • Page 9: Led Indications

    = Access mode is Secure Flashes Green Access has been granted. Flashes Red Access has been denied. Flashes (Blue) Reading and validating a PIV card. 3E4288 Gallagher T10 Reader | Edition 1 | August 2016 Copyright © Gallagher Group Limited Page 9...
  • Page 10: Accessories

    The reader is idle. Peak current during card read. Gallagher T Series readers are UL humidity tested and certified to 85% and have been independently verified to 95%. Note: The current values stated above have been reported using the default configuration for a reader in Command Centre.
  • Page 11: Approvals And Standards

    US - Equipment: com, burg and acc reader CA - Equipment: com, burg reader Please refer to the document “3E2793 Gallagher Command Centre UL Configuration Requirements” for a guide to configuring the Gallagher system to the appropriate UL Standard. 3E4288 Gallagher T10 Reader | Edition 1 | August 2016 Copyright ©...
  • Page 12: Mounting Dimensions

    13 mm (1/2") diameter hole for cable 22.5 mm (0.89") 35 mm (1.38") IMPORTANT This picture is not to scale, therefore use the measurements provided. 3E4288 Gallagher T10 Reader | Edition 1 | August 2016 Copyright © Gallagher Group Limited Page 12...