Download Print this page
ETC Unison Aero UARVSS-5 Installation Manual
ETC Unison Aero UARVSS-5 Installation Manual

ETC Unison Aero UARVSS-5 Installation Manual

Resonate ceiling mount occupancy / vacancy sensor

Advertisement

Quick Links

ETC Installation Guide
Unison Aero
Occupancy / Vacancy Sensor
Overview
The Aero Resonate Ceiling Mount Occupancy / Vacancy Sensor is a
wireless passive Infrared (PIR) vacancy sensor that provides battery-free,
wireless control of lighting, combined with simple installation and
long-term maintenance-free reliability.
The sensor requires no wiring connections and requires no batteries,
although one can be used if needed. In normal operation, charged solar
cells provide power to the sensor.
The sensor communicates with linked Aero power controllers to
manage lighting within interior spaces. The sensor detects the
occupancy or vacancy state of the room by monitoring motion using an
integral passive infrared motion (PIR) detector.
On initial occupancy detection, the sensor broadcasts occupancy
messages to the linked controllers and the loads will turn on. The sensor
repeats the occupied message every 100 seconds until occupancy is no
longer detected, also known as vacancy. After an additional 100
seconds with no motion detected, the sensor transmits a vacancy
message and the linked controllers turn their connected loads off.
Corporate Headquarters
London, UK
Tel +44 (0)20 8896 1000
Rome, IT
Tel +39 (06) 32 111 683
Holzkirchen, DE
Tel +49 (80 24) 47 00-0
Hong Kong
Tel +852 2799 1220
Web:
www.etcconnect.com
Product information and specifications subject to change.
7188M2130
Rev A
Released 2015-06

Resonate Ceiling Mount Sensor
®
Resonate Ceiling Mount
Middleton, Wisconsin, USA
Service: (UK)
Service: (UK)

Service: (DE)

Service: (Asia)

Copyright © 2015 ETC. All Rights Reserved.
Models available
Model
Description
UARVSS-5
Small room 450 feet
UARVSL-5
Large 1800 feet
Tel +608 831 4116
service@etceurope.com
service@etceurope.com
techserv-hoki@etcconnect.com
service@etcasia.com
ETC intends this document to be provided in its entirety.

Page 1 of 10
2
2
(167.2m
Service: (Americas)
service@etcconnect.com
Electronic Theatre Controls, Inc.
2
(41.8m
)
2
)

Advertisement

loading

Summary of Contents for ETC Unison Aero UARVSS-5

  • Page 1   Web: www.etcconnect.com Copyright © 2015 ETC. All Rights Reserved.  Product information and specifications subject to change. ETC intends this document to be provided in its entirety.  7188M2130 Rev A Released 2015-06   Resonate Ceiling Mount Sensor Page 1 of 10 Electronic Theatre Controls, Inc.
  • Page 2: Installation Requirements

    ETC Installation Guide Resonate Ceiling Mount Sensor Installation The installation location of the Resonate Ceiling Mount Occupancy / Vacancy Sensor is important as this will directly impact both it’s performance and the wireless messages that are shared between the sensor and its linked power controllers.
  • Page 3 ETC Installation Guide Control Series Small Room Sensor 8ft/2.4m 10ft / 3m 15ft/4.5m 10ft/3m 5ft/1.5m 5ft/1.5m 10ft/3m 15ft/4.5m Small Room Sensor- use for small motion detection or small rooms • Hand motion is detectable up to 6’ (1.8m) when mounted on an 8’...
  • Page 4: Mounting Location

    ETC Installation Guide Resonate Ceiling Mount Sensor Mounting Location The sensor should be installed in the room where the Aero controller is controlling the light fixtures or circuits, but preferably not on the same vertical wall as the linked power controllers.
  • Page 5: Installing The Sensor

    ETC Installation Guide Control Series Installing the Sensor The recommended mounting location is on the ceiling. Using Integrated Magnets The sensor is provided with integrated magnets allowing installation to a T-bar ceiling frame or other metallic surface by simply aligning the back side of the sensor to the metal rail.
  • Page 6 ETC Installation Guide Resonate Ceiling Mount Sensor Using Tape or Velcro Use double-sided tape or Velcro (not included) to attach the Sensor to a smooth surface. Step 1: Attach two 1.5 inch (4cm) strips of tape or Velcro to the back of the sensor, ensuring they do not extend beyond the edge.
  • Page 7: Lens Masking

    ETC Installation Guide Control Series Step 4: Poke the adapter tines through the ceiling tile, then bend each tine over in opposite directions for a secure fit. Poke the adaptor tines through the ceiling tile, then bend each tine over in opposite directions for a secure fit.
  • Page 8 ETC Installation Guide Resonate Ceiling Mount Sensor Linking the Sensor to a Controller This process requires the sensor to be installed with the cover removed for access to the [Link] button. In addition, the controller or receiver to be linked must be installed, powered, and within range of the sensor.
  • Page 9 ETC Installation Guide Control Series Walk Test Mode Walk Test mode allows an installer to verify the sensor can monitor and detect motion in an area as required. Step 1: Prepare the site for configuration. a: The circuit you are configuring must be powered on.
  • Page 10 ETC Installation Guide Resonate Ceiling Mount Sensor Setting the Sensitivity The Resonate Ceiling Mount Occupancy / Vacancy Sensor sensitivity to motion is configurable to low, medium or high. False occupancy states caused by other elements can be mitigated by reducing the sensitivity level.

This manual is also suitable for:

Unison aero uarvsl-5