Gas Piping; Typical Suspended Furnace / Crawl Space Installation; Gas Valve; Downflow Gas Piping - York PS9 DH Series Installation Manual

High efficiency tubular heat exchanger, single stage downflow/horizontal, 40 - 120 mbh input, 11.72 - 35.17 kw input
Table of Contents

Advertisement

ANGLE IRON
BRACKET
1" MAX. BETWEEN
ROD & FURNACE
6" MIN. BETWEEN
ROD & FURNACE
FIGURE 6: Typical Suspended Furnace / Crawl Space Installation
In any application where temperatures below freezing are possible,
see "BELOW FREEZING LOCATIONS".
SECTION IV: GAS PIPING
GAS SAFETY
An overpressure protection device, such as a pressure regulator,
must be installed in the gas piping system upstream of the furnace
and must act to limit the downstream pressure to the gas valve so it
does not exceed 0.5 PSI {14" w.c. (3.48 kPa)}. Pressures exceed-
ing 0.5 PSI {14" w.c. (3.48 kPa)} at the gas valve will cause damage
to the gas valve, resulting in a fire or explosion or cause damage to
the furnace or some of its components that will result in property
damage and loss of life.
OUTLET
PRESSURE
PORT
INLET
WRENCH
BOSS
INLET
PRESSURE
ON/OFF SWITCH
PORT
(Shown in ON position)
FIGURE 7: Gas Valve
IMPORTANT: Plan your gas supply before determining the correct gas
pipe entry. Use 90-degree service elbow(s), or short nipples and con-
ventional 90-degree elbow(s) to enter through the cabinet access holes.
GAS PIPING INSTALLATION
Properly sized wrought iron, approved flexible or steel pipe must be
used when making gas connections to the unit. If local codes allow the
use of a flexible gas appliance connection, always use a new listed con-
nector. Do not use a connector that has previously serviced another gas
appliance.
Some utility companies or local codes require pipe sizes larger than the
minimum sizes listed in these instructions and in the codes. The furnace
rating plate and the instructions in this section specify the type of gas
approved for this furnace - only use those approved gases. The instal-
lation of a drip leg and ground union is required. Refer to Figure 8.
Unitary Products Group
SUPPORT
BRACKET
1" MAX. BETWEEN
ROD & FURNACE
FIGURE 8: Downflow Gas Piping
FIGURE 9: Horizontal Gas Piping
IMPORTANT: An accessible manual shutoff valve must be installed
upstream of the furnace gas controls and within 6 feet (1.8 m) of the fur-
nace.
The furnace must be isolated from the gas supply piping system by
closing its individual external manual shutoff valve during any pressure
testing of the gas supply piping system at pressures equal to or less
than 1/2 psig (3.5 kPa).
VENT PORT
OUTLET
Never apply a pipe wrench to the body of the gas valve when
installing piping. A wrench must be placed on the octagonal hub
located on the gas inlet side of the valve. Placing a wrench to the
MAIN REGULATOR
body of the gas valve will damage the valve causing improper oper-
ADJUSTMENT
ation and/or the valve to leak.
Gas piping may be connected from either side of the furnace using any
of the gas pipe entry knockouts on both sides of the furnace. Refer to
Figure 3 dimensions.
GAS ORIFICE CONVERSION FOR PROPANE (LP)
This furnace is constructed at the factory for natural gas-fired operation,
but may be converted to operate on propane (LP) gas by using a fac-
tory-supplied LP conversion kit. Follow the instructions supplied with
the LP kit. Refer to Table 6 or the instructions in the propane (LP) con-
version kit for the proper gas orifice size.
HIGH ALTITUDE GAS ORIFICE CONVERSION
This furnace is constructed at the factory for natural gas-fired operation
at 0 – 8,000 feet (0-m – 2,438 m) above sea level.
The manifold pressure must be changed in order to manitain proper
and safe operation when the furnace is installed in a location where the
altitude is greater than 8,000 feet (2,438 m) above sea level. Refer to to
Table 6 for proper manifold pressure settings.
HIGH ALTITUDE PRESSURE SWITCH CONVERSION
For installation where the altitude is less than 8,000 feet (2,438 m), it is
not required that the pressure switch be changed. For altitudes above
8,000 feet (2,438 m), see Field Installed Accessories - High Altitude
pressure Switch.
EXTERNAL MANUAL
SHUTOFF VALVE
TO GAS
SUPPLY
GROUNDED JOINT UNION
MAY BE INSTALLED
DRIP
LEG
INSIDE OR OUTSIDE UNIT.
MANUAL
SHUT-OFF
VALVE
GAS
PIPE
GAS
PIPE
DRIP
LEG
269441-UIM-A-0407
TO GAS
SUPPLY
DRIP
LEG
GAS BURNERS

GAS VALVE

MANUAL
SHUT-OFF VALVE
9