Fujitsu ARU24RGLX Design & Technical Manual page 92

Duct type
Hide thumbs Also See for ARU24RGLX:
Table of Contents

Advertisement

2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function number
26
NOTE: Range of static pressure is different by model.
9-2. Function settings by using remote controller
Setting value
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
31
32
Model name
12//18/24/30/36 model
42/48 model
Setting description
0.12 inWG (30 Pa)
0.16 inWG (40 Pa)
0.20 inWG (50 Pa)
0.24 inWG (60 Pa)
0.28 inWG (70 Pa)
0.32 inWG (80 Pa)
0.36 inWG (90 Pa)
0.40 inWG (100 Pa)
0.44 inWG (110 Pa)
0.48 inWG (120 Pa)
0.52 inWG (130 Pa)
0.56 inWG (140 Pa)
0.60 inWG (150 Pa)
0.64 inWG (160 Pa)
0.68 inWG (170 Pa)
0.72 inWG (180 Pa)
0.76 inWG (190 Pa)
0.80 inWG (200 Pa)
Standard
12/18/24 model: 0.18 inWG (45 Pa)
30/36/42 model: 0.23 inWG (57 Pa)
48 model: 0.28 inWG (70 Pa)
Automatic airflow adjustment
Range of static pressure
0.12 to 0.8 inWG (30 to 200 Pa)
0.12 to 0.72 inWG (30 to 180 Pa)
- 86 -
Factory setting
9. Function settings