High refrigerant pressure
Should the refrigeration pressure rise above 425 PSIG (2930.3 kPA), the high pressure switch contacts will open.
The board sees the open circuit and the HIGH PRESSURE and TIME DELAY LEDs will come on, the machine
shuts down. After the one hour time delay, the machine will attempt to restart. If the pressure has fallen below the
reset point of 295 PSIG (2034.0 kPA) and the board see the contacts closed, the machine will resume normal
operation. If the contacts are still open after the restart, the board will again go into HIGH PRESSURE and TIME
DELAY, cycling until contact closure is seen.