Table of Contents Introduction Proprietary Information Support Support Contacts Returns About this Manual Save this Manual Disclaimer Safety Safety Symbols Battery Safety Battery Warnings and Cautions Specifications Safety Precautions Tools Précautions de sécurité Outils Shipping and Unpacking Placement and Bolt Down Additional Inspection Field Connections Appendix A...
Proprietary Information This document contains information that is confidential and proprietary to ZincFive, Inc. It may not be reproduced, distributed, or translated in any other language, in whole or in part, without written approval from ZincFive and/or its associated partners.
(visit zincfive.com/support or call 888-517-7776). Disclaimer While efforts have been made to ensure the accuracy and validity of information contained in the document, ZincFive assumes no responsibility and disclaims all liability for any errors and/or omissions that may be contained herein.
ZincFive BC Series UPS Battery Cabinet are carefully designed and manufactured to ensure that they are safe and reliable products when used properly. To ensure the safe and proper use of ZincFive BC Series UPS Battery Cabinet, the following symbols are used throughout this manual or on the equipment. Operators, buyers, and technicians must observe each occurrence of these symbols as they appear throughout the document.
Remove the connection from ground if any part of the battery is determined to be grounded. Note: Reference the Z5 12-80 HSF or 13-90 USF Safety Data Sheet for additional battery safety instructions. https://www.zincfive.com/subc-prismatic-material-safety-data-sheet French Cette batterie doit être installée par un personnel qualifié conformément à la dernière édition du National Electrical Code ANSI/NFPA 70 et/ou du Code canadien de l'électricité, Partie I, CSA C22.1.
Retirer le raccordement à la terre si une partie de la batterie est déterminée comme étant mise à la terre. Remarque : Référez-vous à la fiche de données de sécurité du Z5 13-80 HSF ou 13-90 USF pour des instructions supplémen- taires sur la sécurité des batteries. zincfive.com/subc-prismaticmaterial-safety-data-sheet Battery Warnings and Cautions English SHIELD EYES AT ALL TIMES WITH PROTECTIVE GEAR.
Notice: To limit drift in SOC with extended storage, the batteries must not be stored more than six months without recharging. If attached to a UPS that remains de-energized for a long period ZincFive recommends you energize the UPS system every six months for a 12 hour period in order to recharge the batteries.
Si relié à une ASI qui reste inerte pendant une période prolongée, ZincFive vous recommande d'alimenter l'ASI tous les six mois pendant une période de 12 heures afin de recharger les batteries.
For product returns, please contact a ZincFive support representative to obtain a return material authorization (RMA). 5. Save the packaging material in the event a return is needed. ZincFive does not ZincFive, Inc. warranty product damage from return shipping unless it is shipped in approved 20170 SW 112th Ave.
Placement and Bolt Down 1. The Battery Cabinet has several bolt locations for securing to the floor. • Refer to figure below for Bolt Hole location. 2. The cabinet should be placed where it will be mounted, holes marked and 0.75 size bolts placed for anchoring the cabinet.
Field Connections Below are the final connections required prior to going through the power ON sequence. 1. GROUND: Connect the GROUND wire to the GROUND NUT at the top of the cabinet. Figure 3. Knockout and Ground Details 2. DC: Connect the Positive and Negative conductors to the circuit breaker. a.
Page 14
e. Refer to Appendix C for the circuit breaker connection details. 3. AC: Connect the Ground, Neutral and Line to the terminal block for incoming AC. Refer to figures 5 and 6. a. String AC and Neutral connect to fuse holders, strip wiring to 12MM. Torque screws to 1.7Nm (14.75 in-lbs). Wire details: Use 75/90°C rated or higher between #14 to #10 AWG (2.5 to 5.0 mm2) solid/stranded copper.
Page 15
BMS BARRIER STRIP Figure 6. AC Input wiring (on right side at front of cabinet) and ON/OFF Switch NOTES: UNLESS OT CUSTOMER BARRIER STRIP INSTALLATI UVR / SHUN CONNECT UVR - CON SHUNT - CO UNLESS OTHERWISE S DIMENSIONS ARE IN m CAD FILE IS MASTER.
Page 16
Figure 8. BMS and Power Tray Component Layout 6. Connect Ethernet cable to the Faceplate (top left panel inside door) if any remote monitoring of the Battery Cabinet is desired. a. Configuration details are provided in the Operations Manual. 7. Apply AC Power to the system a.
Page 17
Appendix A Installation Instructions | 17...