Table of Contents Introduction Proprietary Information Support Support Contacts Returns About this Manual Save this Manual Disclaimer Safety Safety Symbols Battery Safety Battery Warnings and Cautions Specifications Safety Precautions Tools Précautions de sécurité Outils Shipping and Unpacking Placement and Bolt Down Additional Inspection Field Connections Appendix A...
Proprietary Information This document contains information that is confidential and proprietary to ZincFive, Inc. It may not be reproduced, distributed, or translated in any other language, in whole or in part, without written approval from ZincFive and/or its associated partners.
(visit zincfive.com/support or call 888-517-7776). Disclaimer While efforts have been made to ensure the accuracy and validity of information contained in the document, ZincFive assumes no responsibility and disclaims all liability for any errors and/or omissions that may be contained herein.
ZincFive BC Series UPS Battery Cabinet are carefully designed and manufactured to ensure that they are safe and reliable products when used properly. To ensure the safe and proper use of ZincFive BC Series UPS Battery Cabinet, the following symbols are used throughout this manual or on the equipment. Operators, buyers, and technicians must observe each occurrence of these symbols as they appear throughout the document.
Remove the connection from ground if any part of the battery is determined to be grounded. Note: Reference the Z5 13-80 H S F Safety Data Sheet for additional battery safety instructions. https://www.zincfive.com/subc-prismatic-material-safety-data-sheet French Cette batterie doit être installée dans les applications d’utilisation fin par un personnel qualifié dans l’utilisa- tion sécuritaire des alimentations à...
TENIR HORS DE PORTÉE DES ENFANTS. NE PAS RENVERSER. MAINTENIR À NIVEAU. ATTENTION : RISQUE D'INCENDIE, D'EXPLOSION OU DE BRÛLURES. NE PAS DÉMONTER, CHAUFFER AU-DESSUS DE 75°C, OU INCINÉRER. Specifications Refer to the ZincFive BC Series UPS Battery Cabinet data sheet for specifications. zincfive.com/zincfive-ups-bc-series 8 | Installation Instructions...
Notice: To limit drift in SOC with extended storage, the batteries must not be stored more than six months without recharging. If attached to a UPS that remains de-energized for a long period ZincFive recommends you energize the UPS system every six months for a 12 hour period in order to recharge the batteries.
Si relié à une ASI qui reste inerte pendant une période prolongée, ZincFive vous recommande d'alimenter l'ASI tous les six mois pendant une période de 12 heures afin de recharger les batteries.
(RMA). 5. Save the packaging material in the event a return is needed. ZincFive does not warranty product damage from return shipping unless it is shipped in approved packaging. Carefully move the cabinet to the install location using necessary fork lift / pallet jack a.
Placement and Bolt Down 1. The Battery Cabinet has four bolt locations for securing to the floor. • Refer to figure below for Bolt Hole location. 2. The cabinet should be place where it will be mounted, holes marked, and appropriate size bolts placed for anchoring the cabinet.
Field Connections Below are the final connections required prior to going through the power ON sequence. 1. GROUND: Connect the GROUND wire to the GROUND terminal at the top of the cabinet. • Refer to Appendix B for further details. Figure 4.
Page 14
e. Refer to Appendix C for the circuit breaker connection details. Figure 6. Breaker connection detail 3. AC: Connect the Ground, Neutral and Line to the terminal block for incoming AC. Refer to figures 8 and 9. a. Strip AC wiring to 8mm (5/16”) length. b.
Page 15
Figure 8. AC Input wiring (on right side at back of cabinet) and ON/OFF Switch Figure 9. Pins 1,3 - UVR/Shunt Relay Access, Pins 5,6,7 (NO, COM, NC) 4. UVR/SHUNT and AUX Access: For UPS Systems that require an interface to the Circuit Breaker a customer accessible Terminal Block has been provided.
Page 16
Figure 10. BMS Wiring 6. Connect Ethernet cable to back of the unit if any remote monitoring of the Battery Cabinet is desired. a. Configuration details are provided in the Operations Manual. 7. Apply AC Power to the system a. It will take approximate 1-3 minutes for the BMS/R3000 to initialize and communicate with the server. •...
Page 17
Appendix A Installation Instructions | 17...
Page 18
Appendix B 18 | Installation Instructions...
Page 19
Appendix C Installation Instructions | 19...