Panasonic Intelli-Balance 100 Service Manual page 9

Energy recovery ventilator

Advertisement

4.
Troubleshooting
If a problem is encountered, please investigate it by going through the following items.
If the problem still persists, please disconnect the power and contact the dealer for repair.
Problem
1.The ERV doesn't
work.
2.The HVAC/AHU
doesn't work
when ERV works.
3.Buzzer sound
(10 sec in a hour)
and ERV works.
4.Buzzer sound
(30 sec in a hour)
and ERV doesn't
work.
5.ERV doesn't work
base on the setting
air volume.
The time under "Blink" means the frequency of blink.
*
Display
Running
Filter
indicator
indicator
(Green)
(Red)
Off
Off
On
Off
On
Off
On
On
Blink*
Off
(0.5 s)
Blink*
Off
(2 s)
Blink*
Off
(0.5 s)
Blink*
Off
(2 s)
Blink*
Off
(4 s)
Blink*
On
(0.5 s)
Blink*
On
(0.5 s)
Off
On
Action
Check the power cord is connected.
Check the frame cover is closed.
Check the main switch in product body is on.
Check if the spring on the inside of frame cover
is damaged or deformed.
ERV running interval according to the ASHRAE
time setting.
When outdoor temperature is low (
ERV stops operating automatically.
Damper may be frozen shut, please wait for
maximum 24 hours for defrosting.
Please disconnect the power and contact the
dealer to check the HVAC/AHU wiring connect.
The RA filter and OA filter need to be maintained.
If you do not want the buzzer notification, please
long press the filter reset button for 3 sec to cancel it.
SA motor error, please disconnect the power
and contact the dealer for repair.
EA motor error, please disconnect the power
and contact the dealer for repair.
OA damper error, please disconnect the power
and contact the dealer for repair.
EA damper error, please disconnect the power
and contact the dealer for repair.
Center damper error, please disconnect the
power and contact the dealer for repair.
Temperature sensor error, please disconnect the
power and contact the dealer for repair.
PCB board error, please disconnect the power
and contact the dealer for repair.
When product runs in circulation mode for
defrosting, the air volume will be more than
setting and sound will be slightly louder than
normal operation.
When outdoor temperature is less than 14 °F
(-10 °C), the product will restrict air volume
automatically to protect energy recovery core.
FV-10VEC2H
-22 °F (-30 °C),
8