TE Connectivity Integra INT-2270, INT-2170 - Multifunction Digital Meter Technical Manual

TE Connectivity Integra INT-2270, INT-2170 - Multifunction Digital Meter Technical Manual

Also See for Integra INT-2270:

Advertisement

TE Connectivity Integra INT-2270, INT-2170 - Multifunction Digital Meter Technical Manual

Introduction

The Integra, INT-2270 and Integra INT-2170, are a multifunction digital meter for the measurement of power quality. They provide measurement isolation and conversion of all main electrical parameters. Both INT-2270 and INT-2170 can be used in single and three-phase balanced or unbalanced, 3 or 4 wire electrical systems.
The INT-2270 has an accuracy of CL0.2S.
The INT-2170 has an accuracy of CL0.5S.
Both include RS485 Modbus RTU communications protocol and Pulse/Alarm input/outputs as standard.

Measurement

The device is supplied programmed to the users requirements but can be easily reprogrammed to suit any application.

Setup

The Integra, INT-2*70, is individually calibrated to full accuracy. No further adjustments or setup is required.
Should the unit need reprogramming please refer to the Programming Guide for further information.
Setup

Warnings


Risk of Electric Shock

  • During normal operation, voltages hazardous to life may be present at some of the terminals of this unit.
  • At voltages below that specified in the Range of Use the meter may shut down. However, voltages hazardous to life may still be present at some of the terminals of this unit.
  • Installation and servicing should be performed only by qualified, properly trained personnel abiding by local regulations.
  • Ensure all supplies are de-energised before attempting connection or other procedures.
  • Terminals should not be user accessible after installation and external installation provisions must be sufficient to prevent hazards under fault conditions.
  • This unit is not intended to function as part of a system providing the sole means of fault protection - good engineering practice dictates that any critical function be protected by at least two independent and diverse means.
  • The unit does not have internal fuses therefore external fuses must be used for protection and safety under fault conditions.
  • Never open-circuit the secondary winding of an energized current transformer.
  • This product should only be operated with the CT secondary connections earthed.
  • If this equipment is used in a manner not specified by the manufacturer, protection provided by the equipment may be impaired.
  • During installation suitable PPE, including eye protection MUST be worn at all times.

Safety

The unit is designed in accordance with BS EN 61010-1:2001 (IEC 61010-1:2001) – Permanently connected use, Normal condition. Installation category III, pollution degree 2, basic insulation for rated voltage. Measurement Category III.

Maintenance

In normal use, no maintenance is needed. As appropriate for service conditions, isolate from electrical power, inspect the unit, and remove any dust or other foreign material present. Periodically check all connections for freedom from corrosion and screw tightness, particularly if vibration is present.
The front of the case should be wiped with a dry cloth only. Use minimal pressure, especially over the viewing window area. If necessary wipe the rear case with a dry cloth. If a cleaning agent is necessary, isopropyl alcohol is the only recommended agent and should be used sparingly. Water should not be used. If the rear case exterior or terminals should be contaminated accidentally with water, the unit must be thoroughly dried before further service. Should it be suspected that water might have entered the unit, factory inspection and refurbishment is recommended.


It is essential that the primary current is isolated BEFORE connecting or disconnecting the secondary current connections
The unit is intended for panel mounting. Avoid mounting the unit where there is excessive vibration; in excessive direct sunlight; or outside a reasonably stable ambient temperature.

Connection Diagram

Connection Diagram

CONNECTION DETAIL - Part 1
CONNECTION DETAIL - Part 2
CONNECTION DETAIL

warning REFER TO MANUAL

EMC Installation Requirements

Whilst this unit complies with all relevant EU EMC (electromagnetic compatibility) regulations, any additional precautions necessary to provide proper operation of this and adjacent equipment will be installation dependent and so the following can only be general guidance:

  • Avoid routing wiring to this unit alongside cables and products that are, or could be, a source of interference.
  • The supply to the unit should not be subject to excessive interference. In some cases, a supply line filter may be required.
  • To protect the product against incorrect operation or permanent damage, surge transients must be controlled. It is good EMC practice to suppress transients and surges at the source. The unit has been designed to automatically recover from typical transients; however in extreme circumstances it may be necessary to temporarily disconnect the supply for a period of greater than 10 seconds to restore correct operation.
  • Screened communication leads are recommended and may be required. These and other connecting leads may require the fitting of RF suppression components, such as ferrite absorbers, line filters etc., if RF fields cause problems.
  • It is good practice to install sensitive electronic instruments that are performing critical functions in EMC enclosures that protect against electrical interference causing a disturbance in function.

Wiring

Connections are made via shrouded screw-clamp 0.05-4mm wire. Choice of cable should meet local regulations for the operating voltage.
Connector plugs are suitable for copper wires only and will accept one stranded 0·05 – 4mm2 (30 - 11AWG) stranded core cables. This instrument is intended for panel mounting. Terminals must be enclosed within the panel. For mains terminals use wire rated at 1000V, 60°C minimum temperature. Terminal screws are fully tightened for shipment and must be undone before wire insertion. Terminal screws should be tightened to 0·5 Nm (4·4 lbf in) only.

Fusing

This unit must be installed with external fuses in the voltage supply lines of type slow blow 1A maximum. Choose fuses of a type and with a breaking capacity appropriate to the supply and in accordance with local regulations.
A suitable switch or circuit breaker conforming to the relevant parts of IEC 60947-1 and IEC 60947-3 should be included in the installation. It should be positioned so as to be easy to operate, in close proximity to the equipment, and clearly identified as the disconnecting device.

Specification

System Input
Nominal input voltage 57.7 to 364V AC L-N
(100 – 600V AC L-L)
720V MAX
Max. continuous input overload voltage 120% of nominal
Max. short duration input Voltage 2 x range maximum
Nominal input voltage burden < 0·2VA all phases
Nominal input current 1 or 5 A
Max. short duration input current 20 x nominal
(for 300msec)
Frequency 45 to 65Hz
Supply burden 10 VA
Range of Use
Values of measured quantities, components of measured quantities, and quantities which affect measurement errors to some degree, for which the product gives meaningful readings:
Voltage 5... 120% of nominal
Current 5... 120% of nominal
Active power 50... 120% of nominal
Apparent power 50... 120% of nominal
Power is only registered when voltage and current are within their respective range of use.
Accuracy (INT-2270)
Voltage (V) < 0·2% of reading
Current (A) < 0·2% of reading
Neutral current calculated (A) < 1% of reading
Frequency (Hz) < 0.1 Hz
Active power (W) ± 0.2% of reading CL0.2S
Reactive power (VAr) ± 0.2% of reading CL0.2S
Apparent power (VA) ± 0.2% of reading CL0.2S
Active energy (kWh) Class 0.2
(IEC 62053-21) section 4.61
Reactive energy (kVArh) Class 1 IEC 62053-23 2
THD up to 63rd harmonic
Accuracy (INT-2170)
Voltage (V) < 0·5% of reading
Current (A) < 0·5% of reading
Neutral current calculated (A) < 1% of reading
Frequency (Hz) < 0.1 Hz
Active power (W) ± 0.5% of reading CL0.5S
Reactive power (VAr) ± 0.5% of reading CL0.5S
Apparent power (VA) ± 0.5% of reading CL0.5S
Active energy (kWh) Class 0.5
(IEC 62053-21) section 4.61
RS485 / Modbus RTU output
Type 2-wire half duplex
Baud rate 9600, 19200, 38400
*Ensure any external circuits connected to RS-485 output modules are provided with double/reinforced insulation.
Pulsed Output
Two voltage-free pulse outputs for measuring active and reactive energy.
The pulsed output is used as an option with Alarm Outputs.
Output Type Solid State Relay
Contact Rating 50mA max at 250V AC
Isolation 2.5 kV
Pulsed Duration 60, 100, 200mSecs
Pulsed Rate Divisors Range 1 pulse per Wh up to 1 pulse per GWh
Pulsed Output Allocation Import / Export kWh / KVArh
Energy Units Unit, Kilo, Mega, Giga
Limited Max Pulse rate 2 pulses per sec
Alarm Output
Used instead of pulsed outputs in any configuration.
Type User defined Solid State Relay
Pulse duration 30msec to 1000 msec
Alarm Delay 0-120 secs
Hysteresis 1 – 99%
Inputs
Pulsed inputs from a galvanically isolated open collector source.
Input Voltage Range 0 to 24V DC
Input current (max) 2.0 mA @ 24V DC
Switch response time 0.5 secs
(Latency to respond to pulse event)
Pulse frequency (max) 25Hz (20ms)
Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy is verified under nominal value (within the specified tolerance) of these conditions.
Ambient temperature 23°C ±1°C
Input waveform 50 or 60Hz ±2%
Input waveform Sinusoidal (distortion factor<0·005)
Magnetic field of external origin Terrestrial flux
Environment
Operating temperature -20°C to +60°C*
Storage temperature 30°C to +80°C*
*Maximum operating and storage temperatures are in the context of typical daily and seasonal variation.
Relative humidity 0 to 95%, non-condensing
Altitude Up to 2000m
Warm up time 1 minute
Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
Shock 30g in 3 planes, IEC 60068-2-6, 2g
Dielectric voltage 2.5kV, 50Hz for 1 minute
Withstand test supply/inputs/outputs
Mechanics
Dimensions 96 x 96 DIN
4.3" x 4.3" ANSI
Depth Front of Panel19.9mm (0.78") Rear of Panel 78.3mm (3.00")
Sealing IP52 (front panel), IP30 (rear)
Mounting Panel Mounted DIN96, ANSI
Cutout DIN 96 92mm x 92mm square
ANSI C39.1 4" round

Dimensions

Standards and Approvals

Electromagnetic compatibility
Electrostatic discharge IEC 61000-4-2
Immunity to radiated fields IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to Impulse waves IEC 61000-4-5
Conducted immunity IEC 61000-4-6
Immunity to magnetic fields IEC 61000-4-8
Immunity to voltage dips IEC 61000-4-11
IEC 61326-1, Class A
Accuracy
Static meter for active energy (Class 0.2S) IEC 62053-21 IEC 62053-22
Active energy accuracy ANSI C12.20
Static meter for reactive energy (Class 0.5S) IEC 62053-23
Safety
CE Marking IEC 61010-1
Ed.3
IEC 62052-11
Features
Sag / Swell IEC 50160

Explanation of Symbols

warning Refer to manual
shock hazard Danger of electric shock
Do not discard

While TE has made every reasonable effort to ensure the accuracy of the information in this catalogue, TE does not guarantee that it is error-free, nor does TE make any other representation, warranty or guarantee that the information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to the information contained herein at any time without notice. TE expressly disclaims all implied warranties regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or fitness for a particular purpose. The dimensions in this catalogue are for reference purposes only and are subject to change without notice. Specifications are subject to change without notice. Consult TE for the latest dimensions and design specifications. TE connectivity (logo), TE (logo) and TE Connectivity are trademarks of the TE Connectivity Ltd. family of companies. Crompton is a trademark of Crompton Parkinson and is used by TE Connectivity under a licence. Other logos, product and company names mentioned herein may be trademarks of their respective owners

TE Energy – innovative and economical solutions for the electrical power industry: cable accessories, connectors & fittings, insulators & insulation, surge arresters, switching equipment, street lighting, power measurement and control.

Tyco Electronics UK Ltd
TE Energy
Freebournes Road
Witham, Essex CM8 3AH
Phone: +44 (0)870 870 7500
Fax: +44 (0)870 240 5289
Email: Crompton.info@te.com

www.crompton-instruments.com

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download TE Connectivity Integra INT-2270, INT-2170 - Multifunction Digital Meter Technical Manual

Advertisement

Need help?

Need help?

Do you have a question about the Integra INT-2270 and is the answer not in the manual?

Questions and answers

Table of Contents