To Connect The Shut-Off Valve; To Connect The Electricity Meters - Daikin EHVZ08S23DA6V Installation Manual

Hide thumbs Also See for EHVZ08S23DA6V:
Table of Contents

Advertisement

4 Installation
a
X6M
F1B
b
Q1DI
a
Factory-mounted cable connected to the backup heater
contactor inside the switch box (K5M for *6V and *9W
models)
b
Field wiring (see table below)
Model (power
Connections to backup heater power
supply)
*6V (6V: 1N~ 230 V)
SWB
F1B
1N~, 50 Hz
230 V AC
*6V (6T1: 3~ 230 V)
K5M
SWB
F1B
Q1DI
3~, 50 Hz
230 V AC
Installation manual
14
supply
2
4
6
14
K5M
1
3
5
13
X6M
1
3
5
7
I
I
I
I
2
4
6
8
Q1DI
L
N
2
4
6
14
1
3
5
13
X6M
1
3
5
7
I
I
I
I
2
4
6
8
L1 L2 L3
Model (power
Connections to backup heater power
supply)
*9W (3N~ 400 V)
SWB
F1B
Q1DI
3N~, 50 Hz
400 V AC
F1B
Overcurrent fuse (field supply). Recommended fuse for *6V
and *9W models: 4‑pole; 20 A; curve 400 V; tripping class
C.
K1M
Contactor (in the lower switch box)
K5M
Safety contactor (in the lower switch box)
Q1DI
Earth leakage circuit breaker (field supply)
SWB
Switch box
X6M
Terminal (field supply)
NOTICE
Do NOT cut or remove the backup heater power supply
cable.
4.5.5

To connect the shut-off valve

INFORMATION
Shut-off valve usage example. In case of one LWT zone,
and a combination of underfloor heating and heat pump
convectors, install a shut-off valve before the underfloor
heating to prevent condensation on the floor during cooling
operation. For more information, see the installer reference
guide.
1 Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
NOTICE
Wiring is different for a NC (normally closed) valve and a
NO (normally open) valve.
NO
M2S
21 28
X2M
X1M
2 Fix the cable with cable ties to the cable tie mountings.
4.5.6

To connect the electricity meters

INFORMATION
In case of an electrical meter with transistor output, check
the polarity. The positive polarity MUST be connected to
X5M/6 and X5M/4; the negative polarity to X5M/5 and
X5M/3.
EHVZ04+08S18+23DA + EHVZ04+08S18+23DJ
supply
2
4
6
14
K5M
1
3
5
13
X6M
1
3
5
7
I
I
I
I
2
4
6
8
L1 L2 L3
N
NC
M2S
21 29
X2M
X1M
Daikin Altherma 3 R F
4P584429-1 – 2019.06