• Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
• Be sure to execute heat insulation on the drain
piping.
Unit: mm
Hanging bar
a
Upward routing not allowed
a
- Heat insulation material: Polyethylene foam
with thickness more than 8 mm.
Drain test
The air conditioner uses a drain pump to drain
water.
Use the following procedure to test the drain pump
operation:
• Connect the main drain pipe to the exterior and
leave it provisionally until the test comes to the
end.
• Feed water to the flexible drain hose and check
the piping for leakage.
• Be sure to check the drain pump for normal
operating and noise when electrical wiring is
complete.
• When the test is complete, connect the flexible
drain hose to the drain port on the indoor unit.
Feed water
a
Drain pan
c
Flexible drain hose
e
(Accessory)
Glue the joint.
g
Drain hose connection - Use the clip
h
(Accessory)
CAUTION
• The supplied flexible drain hose should not be
curved, neither screwed. The curved or screwed
hose may cause a leakage of water.
Flexible drain hose
a
Heat insulation
• Use the heat insulation material for the
refrigerant piping which has an excellent heat-
resistance (over 120°C).
• Precautions in high humidity circumstance: This
air conditioner has been tested according to the
"KS Standard Conditions with Mist" and
INSTALLATION
Drain pump
b
Drain port
d
Main drain pipe
f
13