Table of contents 1.WHP03300PSV-F8JUN Specifications ————————1~4 1. Application range 2. Compressor Specifications 3. List of parts and drawings 4. general characteristics 2. Benchmarks for Rotary Compressors ———————5~10 1. System Design Constraints 2. Process limitations 3. O t h e r 3.
Page 3
SUBJECT PAGE:1/22 Model WHP03300PSV-F8JUN SPECIFICATION 1. SCOPE This specification is applied to SHANGHAI HIGHLY rotary compressor. SPECIFICATION OF COMPRESSOR WHP03300PSV-F8JUN 2.1 Model 2.2 Rated Voltage-Frequency-Phase 220V~240V/50Hz/ 2.3 Application Heat pump water heater R-290 2.4 Refrigerant 2.5 Compressor Cooling Forced air 17.0ml/rev 2.6 Displacement single-cylinder...
Page 4
SUBJECT PAGE:2/22 Model WHP03300PSV-F8JUN SPECIFICATION 2.16 Hermetic Terminal 1/4”quick connect type 2.17 Motor Type Permanent Split Capacitor Capacitor 25μ F /400 V Locked rotor amps 21.0A (at 240V) Approved voltage range Rated voltage±10% 3.74/4.35 Ω (at 20℃) Winding resistance(M/S) 2.18 Rated conditions Voltage 220V Evaporating temp.
Page 5
SUBJECT PAGE:3/22 Model WHP03300PSV-F8JUN SPECIFICATION TABLE 1 Starting Conditions Spec Pressure Starting voltage Motor temperature MPa{kgf/ Cold-Starting Below 85% of rated voltage Cold state (room temperature) 1.027{9.46} Hot-Starting(Standard) Below 85% of Hot state after operated under rated voltage standard load condition 0.984{9.02} Hot-starting(Overload) Below 90% of...
Page 6
SUBJECT PAGE:4/22 Model WHP03300PSV-F8JUN SPECIFICATION 3. PARTS AND DRAWING LIST DRAWING NO. PARTS NAME QTY/SET REMARKS Compressor Dimensioned sketch Mounting Mount Assy SC01DA55 parts Rubber mount SC01DA68 Electrical Terminal cover 4CYC01233 parts Packing 4CYC01234 Flange nut SC01D430 Run capacitor SC01D352H18 * Lead routing 4CYC01235 Performance curve...
Page 7
ROTARY COMPRESSOR CRITERIA FOR LONG LIFE PAGE:5/22 REFRIGERATION SYSTEM SYSTEM DESIGN LIMITATIONS 1.1 Powersource and Voltage Voltage applied to hermetic terminal should be within the range mentioned in this specification. In the case of three phase, the phase imbalance should be within 3% among the compressor terminals.
Page 8
ROTARY COMPRESSOR CRITERIA FOR LONG LIFE PAGE:6/22 REFRIGERATION SYSTEM Table 2 Item Operating Envelope 3.13 {30.91}MAX Discharge pressure (see graph 1) (condensing temperature :80℃) MPa{kgf/cm 0.168~0.95 {0.678~8.67} Suction Pressure (Evaporation Temperature : MPa{kgf/cm -30℃~25℃) Compressor case 99℃or below and 6 degrees bottom temp higher than condensing temperature Voltage ±10%...
Page 9
ROTARY COMPRESSOR CRITERIA FOR LONG LIFE PAGE:7/22 REFRIGERATION SYSTEM raph 1 Condensing temperature 75℃ 25℃ 10℃ 10℃ 65℃ 80℃ 80℃ 80℃ Evaporation Temperature 25℃ 25℃ 10℃ -30℃ -30℃ -10℃ -5℃ 10℃...
Page 10
ROTARY COMPRESSOR CRITERIA FOR LONG LIFE PAGE:8/22 REFRIGERATION SYSTEM The system should not flood back liquid to the compressor under all conditions. There should be superheated gas returned to the compressor under all normal operating conditions. 1.5 Allowable Incline The allowable incline should be less than 5 during operation. 1.6 Pipe Vibration The displacement of the pipes, which connect from the compressor to other parts of the refrigerator systems, should be less than 0.8mm(1/32”)when...
Page 11
ROTARY COMPRESSOR CRITERIA FOR LONG LIFE PAGE:9/22 REFRIGERATION SYSTEM PROCESS LIMITATIONS The manufacturing process of refrigerating system must comply with the regulations related to flammable refrigerants, since R290 is flammable refrigerant. The degree of vacuum in the refrigerating system should be less than 20Pa {150×10-3mmHg}at room temperature just before charging refrigerant.
Page 12
ROTARY COMPRESSOR CRITERIA FOR LONG LIFE PAGE:10/22 REFRIGERATION SYSTEM MISCELLANY 3.1 The pipe and hermetic pens attached to the compressor should not be bent. 3.2 The compressor should never be operated while under vacuum;otherwise, internal arcing can cause damaging parts. 3.3 The compressor should not be operated to form a vacuum and to absorb air.
Page 13
ROTARY COMPRESSOR CRITERIA FOR LONG PAGE:11/22 LIFE REFRIGERATION SYSTEM 3.13 The first starting voltage supplied to the refrigerating system should be more than the starting voltage mentioned TABLE 1(page 3). 3.14 The compressor should be kept out of the corrosive atmosphere such as in a chemicals storage, beside a hot spring and so on.
Page 14
Check upon Delivery PAGE:12/22 1. Basis for Checking upon Delivery The Performance test will be carried out in accordance with this “compressor specification”. The Safety Performance in accordance with GB4706.1 Safety of household and similar electrical appliances General requirements and GB 4706.17 Safety of household and similar electrical appliances Particular requirements for motor-compressor.