Hitachi RAS-34FSN Installation & Maintenance Manual page 24

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

Table 6.1 Electrical Data and Recommended Wiring, Breaker Size/1 Outdoor Unit
Model
Power Supply
RAS-34FSN
RAS-36FSN
RAS-38FSN
220V/60Hz
RAS-40FSN
RAS-42FSN
RAS-34FSN
RAS-36FSN
380-415V/50Hz
RAS-38FSN
380V/60Hz
RAS-40FSN
RAS-42FSN
ELB: Earthleakage Breaker
MLFC: Flame Retardant Polyflex Wire
I Field Minimum Wire Sizes for Power Source
Model
Power Source
RAS-34FSN
RAS-36FSN
RAS-38FSN
220V/60Hz
RAS-40FSN
RAS-42FSN
RAS-34FSN
RAS-36FSN
380-415V/50Hz
RAS-38FSN
380V/60Hz
RAS-40FSN
RAS-42FSN
* Refer to the NOTES: in the next page for selection of the power source cable size.
NOTES:
1) Follow local codes and regulations when selecting field wires.
2) The wire sizes marked with *1 in the table of this page are selected at the maximum current of the unit according to
the European Standard, EN60 335-1. Use the wires which are not lighter than the ordinary tough rubber sheathed
flexible cord (code designation H05RN-F) or ordinary polychloroprene sheathed flexible cord (code designation
H05RN-F).
3) The wire sizes marked with *2 in the table of this page are selected at the maximum current of the unit according to
the wire, MLFC (Flame Retardant Polyflex Wire) manufactured by Hitachi Cable Ltd., Japan.
4) Use a shielded cable for the transmitting circuit and connect it to ground.
5) In the case that power cables are connected in series, add each unit maximum current and select wires below.
Selection According to EN60 335-1
Current i (A)
Wire Size (mm
i ≤ 6
6 < i ≤ 10
10 < i ≤ 16
16 < i ≤ 25
25 < i ≤ 32
32 < i ≤ 40
40 < i ≤ 63
63 < i
Install a multi-pole main switch with a space of 3.5mm or more between each phase.
20
Max.
Running
Current
(A)
115
123
130
138
143
64
68
72
76
79
Maximum
Current
115
123
130
138
143
64
68
72
76
79
Selection According to MLFC (at Cable Temperature of 60
2
)
Current i (A)
i ≤ 18
0.75
18 < i ≤ 24
1
24 < i ≤ 34
1.5
34 < i ≤ 47
2.5
47 < i ≤ 62
4
62 < i ≤ 78
6
78 < i ≤ 112
10
112 < i ≤ 147
*3
147 < i ≤ 179
Power
Supply
Nominal
Line
Current
2
(A)
(mm
)
MLFC38SQ
200
MLFC38SQ
200
MLFC50SQ
200
MLFC50SQ
200
MLFC50SQ
200
MLFC22SQ
125
MLFC22SQ
125
MLFC22SQ
125
MLFC22SQ
125
MLFC22SQ
150
Power Source Cable Size
EN60 335-1
MLFC
*1
*2
2
-
38mm
-
2
38mm
-
2
50mm
-
2
50mm
-
2
50mm
2
-
22mm
-
2
22mm
-
2
22mm
-
2
22mm
-
2
22mm
Wire Size (mm
2
)
0.75
1.25
2
3.5
5.5
8
14
22
30
ELB
Nominal
Fuse
Sensitive
Current
(mA)
(A)
100
125
100
125
100
150
100
150
100
150
100
70
100
70
100
80
100
80
100
80
Transmitting Cable Size
EN60 335-1
MLFC
*1
*2
2
0.75mm
0.75mm
o
C)
*3: In the case that
current exceeds 63A,
use MLFC cables.
2