NOTE: Horizontal flue pipes should always be installed with a fall of at least 1.5° 
from the terminal to allow condensate to run back to the boiler.
page 21
8.2 Twin & Vertical Flue Systems
1. Maximum permissible equivalent flue lengths are:­
 
Vertical Concentric 10 metres 20 metres
Vertical Twin Pipe 15 metres  
2. Any additional "in line" bends in the flue system must be taken into consideration.
Their equivalent lengths are:­
Concentric
Pipes:
135° bend
 
93° bend
Twin Flue Pipe  
 
135° bend 0.25 metres
(60/100)
(80/125)
0.5 metres
1.0 metres
 