When Tr is between the Ts and Ts+2 , the outdoor system will be operated at the high dehumidifying
frequency for 10 minutes and then at the low dehumidifying mode for six minutes. The indoor fan will
operate at low speed.
When Tr< Ts, the outdoor system will be stopped, the indoor fan will be stopped for 3 minutes and then
turned to the low speed option.
All the frequency converses have a
* Wind speed control: Automatic:
When Tr≥ Ts+ 5 , high speed.
When Ts+3 ≤Tr< Ts+5 , medium speed.
When Ts+2 ≤Tr< Ts+3 , low speed.
When Tr<Ts+2 , light speed.
If the outdoor fan stopped, the indoor fan will be paused for 3 minutes.
If the outdoor fan stopped for more than 3 minutes and the outdoor system still operates, the system will be
changed into light speed mode.
When the airflow speed has no delay from the high to low switching, the speed should be delayed for 3
minutes (remain at high speed for 3 minutes.) before the next switch.
Manual: When the sensor is off or Tr< Ts+3 , the manual operation can not be made. (obligatory automatic
operation.)
*Airgate location control: the location for the airgate can be set according to your needs.
7.1.4
Heating operation mode.
* temperature control range: 16---30
* temperature difference:
* control feature: the temperature compensation is automatically added and the system will send the heating
signals to the outdoor system.
If Tr≤Ts, the outdoor compressor is turned on, the indoor fan will be at the cold air proof mode.
If Tr>Ts+1 , the outdoor system is turned off, the indoor fan will be at the heat residue sending mode.
If Tr<Ts-1 , the outdoor system will be turned on again, the indoor fan will be at the cold air proof mode.
*Indoor fan control
manual control: You can choose high, medium, low and automatic speed control.
Automatic: When Tr<Ts, high speed.
When Ts≤Tr≤Ts+2 , medium speed.
When Tr> Ts+2 , low speed.
When the airflow speed has no delay from the high to low switching, the speed should be delayed for 3
minutes (remain at high speed for 3 minutes.) before the next switch.
*Airgate location control: the location for the airgate can be set according to your needs.
Coldair proof operation
1
difference.
±1
19
Functions and control