(6) SWING (
) mode
By selecting SWING mode with VANE CONTROL button, the horizontal vanes swing vertically.
When COOL, DRY or FAN mode is selected, only the upper vane swings.
(7) Cold air prevention in HEAT operation
The horizontal vane position is set to Upward.
(8) ECONO COOL ( ) operation (ECONOmical operation)
When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 4°F(2°C) higher by
microprocessor. However, the temperature on the LCD screen on the remote controller is not changed.
Also the horizontal vane swings in various cycle.
SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher, the
air conditioner can keep comfort. As a result, energy can be saved.
To cancel this operation, select a different mode or press one of the following buttons in ECONO COOL operation:
ECONO COOL, WIDE VANE CONTROL or VANE CONTROL button.
2. Vertical vane
(1) Press WIDE VANE CONTROL button to change horizontal airflow direction.
•The vertical vane moves for about 30 seconds.
(After 30 seconds, the vertical vane moves to its original position. In this case, press WIDE VANE CONTROL button
again.)
(2) Press WIDE VANE CONTROL button again to set horizontal airflow direction.
•The vertical vane stops and the airflow direction is set.
(3) Positioning
To confirm the standard position, the vane moves until it touches the vane stopper. Then the vane set to the desired
angle.
Confirming of standard position is performed in the following cases:
(a) When STOP/OPERATE(OFF/ON) button is pressed (POWER ON).
(b) When SWING is started.
8-7. DRAIN PUMP/ FLOAT SENSOR CONTROL
1. Drain pump
Operating condition:
1. During COOL, DRY, or emergency COOL operation
2. When float sensor detects water level above fixed point during:
(a) HEAT operation.
(b) emergency HEAT operation.
(c) standby when during multi system operation.
(d) standby when ON timer is set.
(e) operation STOP.
Drain pump operates in conditions 1 or 2.
Operation stop condition:
Condition other than 1 or 2 indicated above.
2. Float sensor
Float moves with the up and down of water surface inside the drain pan, and judges water level.
(Fixed point differs at raised and lowered water levels.)
Fixed point, when water level rises
Fixed point, when water level lowers
OBHT802B
Float sensor
Water surface
16