Rayleigh Instruments RI-ENERGYFLOW 3P Series User Manual

Rayleigh Instruments RI-ENERGYFLOW 3P Series User Manual

Solar inverter

Advertisement

Quick Links

Rayleigh Instruments Limited
Raytel House, Cutlers Road, South Woodham Ferrers, Chelmsford, Essex CM3 5WA. UK
RI-ENERGYFLOW-3P-SERIES-25
3P-SERIES-25
Solar Inverter
User Manual
www.rayleigh.com
Telephone : +44 (0) 1245 428500
Email : sales@rayleigh.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RI-ENERGYFLOW 3P Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Rayleigh Instruments RI-ENERGYFLOW 3P Series

  • Page 1 Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com RI-ENERGYFLOW-3P-SERIES-25 3P-SERIES-25 Solar Inverter User Manual Rayleigh Instruments Limited www.rayleigh.com Raytel House, Cutlers Road, South Woodham Ferrers, Chelmsford, Essex CM3 5WA. UK...
  • Page 3: Table Of Contents

    Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com Content 1. Introduction ................................1.1 Introduction ........................................1.2 Applied designations ......................................1.3 Important safety information ................................1.4 System sizing ......................................... 2. Technical description of inverters ..........................2.1 Mechanical design ....................................2.2 Electrical system design ....................................
  • Page 4: Introduction

    1. Introduction 1.1 Introduction This manual describes solar inverters : RI-ENERGYFLOW-3P-SERIES25-10KW /15KW /17KW /20KW /25KW. These inverters are transformerless based inverter. 1.2 Applied designations CE Mark UK CA Mark 1.3 Important safety information...
  • Page 5: System Sizing

    Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com Before installation: Installation: Disconnecting the inverter: Operating the inverter: should be used. Functional safety parameters: 1.4 System sizing inverter. considered in each individual case.
  • Page 6: Technical Description Of Inverters

    2. Technical description of inverters 2.1 Mechanical design Figure 2-1 shows the outline dimensions and electrical terminals of: RI-ENERGYFLOW-3P-SERIES-25-10KW /15KW /17KW /20KW /25KW: 510.00 185.00 ① ② ③ ④ ⑤ Figure 2-1 Outline dimensions AC terminal 2.2 Electrical system design RTER FAULT PROTECT O DC/DC...
  • Page 7: Technical Data

    Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com 2.3 Technical data RI-ENERGYFLOW-3P-SERIES-25- 10KW 15KW 17KW 20KW 25KW DC Input Data 15000 W 22500 W 25500 W 30000 W 37500 W 1100 150 ~ 1000 ( Rated Input Voltage 630V 1 / 1 2 / 1 2 / 2...
  • Page 8 General Data 506 386 185mm Communication -25℃ ~ 60℃ Relative Humidity < 0.2W Transformerless Protection Grades < 30dB < 45dB Warranty 5 / 7 / 10 years *1: The maximum DC input current for RI-ENERGYFLOW-3P-SERIES-25-25KW is 37.5A...
  • Page 9: Grid Codes

    Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com 2.4 Grid codes National / Regional Grid Code Description AS4777 RD1699 Greece C10/11 China BDEW-DE Korea China-W : : Brazil : : PEA-W : : : : MEA-W : : Tunisia Tunisia-W :...
  • Page 10: Installation And Startup

    3. Installation and startup Warning! Before installation and maintenance ensure that both the AC and DC sides are fully isolated. Note that if the DC side is just disconnected the capacitors still retain charge. Wait at least 5 minutes to ensure that the capacitors have fully discharged all residual energy before proceeding with any installation or maintenance.
  • Page 11: Installation Position

    Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com No sun No rain No snow Sunlight Rain Snow Figure 3-2 installation environment 3.3 Installation position Figure 3-2 installation position 500mm 300mm 300mm 300mm 500mm Figure 3-3 Distance required of Invertors...
  • Page 12: Mounting Procedure

    3.4 Mounting procedure Step 1: Drill 4 x Ø10mm holes in the wall as dimensions below. Step 2: A x the mounting bracket to the wall using the 4 expansion bolts supplied in the accessories bag. Step 3: Hang the inverter on the wall-mounted bracket and secure it in place using the fixing screws. 400mm 50mm 4 x Ø10mm holes - depth 50mm...
  • Page 13: Electrical Connection

    Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com 3.5 Electrical connection 3.5.1 Connection to the grid (AC output) wire and earth wire is less than 10ohm. Connect the inverter to the grid: 1) Scrip off PE/N/L1/L2/L3 cables as figure below: Description Remark Protective layer diameter...
  • Page 14 5) The cables are inserted into the terminal accord- 6) Insert the main part of AC connector into the ing to the wire sequence (L1/L2/L3/N/PE), so that terminal and hear a "click" sound. the insulating terminal is flush with the surface of the terminal, and the crimping screw torque is 2.0±0.1N•m.
  • Page 15: Connection To Pv String (Dc Input)

    Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com 3) Hold the unlocking nut with one hand and 4) Use a screwdriver to peel off the positions (both rotate it in the direction of the mark, and turn the nut sides) indicated by the red circle to complete the in the opposite direction.
  • Page 16: Communication

    3.5.3.1 WIFI/GPRS Communication (optional) Connect the WIFI/GPRS module produced by Rayleigh Instruments to the COM1 port of inverter. After successful connection, information such as power generation and running state of the inverter can be viewed via the App on the phone. For details please refer to the module user manual.
  • Page 17 Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com 3.5.3.2 Smart Energy Meter Connection (Optional) The inverter is equipped with the feed-in power limit function, and the communication port for smart energy meter is COM2, below is the method of connecting the smart meter in system. COM2 Figure 3-19 3.5.3.3 DRM connection...
  • Page 18: Starting The Inverter

    3.6 Starting the Inverter Before turning on the inverter, please confirm the following:- 1 ) The three-phase (five wires - PE/L1/L2/L3/N) cable is correctly connected to the inverter AC side through an AC circuit breaker; 2) The DC cable is correctly connected to the inverter DC side through a DC circuit breaker. Ensure the correct connection of the two strings and their polarity.
  • Page 19: Lcd Display

    Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com 4.2 LCD display Normal/Fault Pac = Set Language English Factory Set Factory Set Vpv1: Pac = Portuguese Set Country Factory Set Factory Set Ipv1X Pac = VDE4105 Vpv2X Factory Set Factory Set Pac = EN50549 Ipv2X...
  • Page 20: Setting Language

    4.4 Setting language 4.5 Setting modbus address 4.6 Self-Test in accordance with CEI 0-21 (Applies to Italy only) Auto-Test from screen: AutoTest-Italy 0-21 Pac= 10000W...
  • Page 21 Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com 253.0V/251.1V 223.3V/1993ms 253.0V/243.9V 223.3V/1993ms 264.5V/232.6V 223.8V/187ms 195.5V/213.0V 223.5V/1485ms 34.5V/36.2V 226.4V/190ms 50.20Hz/49.88Hz 49.98Hz/95ms 49.80Hz/49.88Hz 50.03Hz/88ms 51.50Hz/51.39Hz 50.04Hz/93ms 47.50Hz/48.01Hz 50.01Hz/91ms...
  • Page 22: Warranty

    Solar Admin COM1 History info Protection other 253.0 224.0 264.5 230.5 195.5 230.2 2000 1987 1500 1486 Pass Pass Pass Fmin 34.5 225.0 50.2 50.01 49.8 49.94 AUTOTEST Pass Pass Pass Fmin Read 51.5 51.02 47.50 50.03 Pass Pass 5. Warranty Once the product has been installed and operational, it is paramount to register the product to initiate the Warranty cover, without this, your product would not be covered under our warranty scheme.
  • Page 23: Service After Warranty Expiration

    Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com 5.2 Service after warranty expiration 6. Troubleshooting and Maintenance 6.1 Troubleshooting Fault LCD display Possible actions restarts. Fault OFR Fault UFR 1 . Grid is not connected. Clearable Fault cooler environment. call local service.
  • Page 24: Maintenance

    Fault LCD display Remark RelayFail BusUnbalance EEPROM_W Fail EEPROM_R Fail Permanent Fault SciCommLose BusFault CPU ADFault PLLFault AutoTestFail FanError 6.2 Maintenance • NOTICE contact Rayleigh Instruments Otherwise, Rayleigh Instruments shall not be held liable for any damage caused.
  • Page 25: Routine Maintenance

    Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com 6.2.1 Routine Maintenance Item Method Period System clean the inverter enclosure if necessary. Check if the air inlet if necessary. Fans Once a year Cable entry Once a year Electrical Connection the metal enclosure.
  • Page 27 Telephone : +44 (0) 1245 428500 Email : sales@rayleigh.com...
  • Page 28 Raytel House, Cutlers Road, South Woodham Ferrers, Chelmsford, Essex CM3 5WA. United Kingdom. Telephone : +44 (0)1245 428500 www.rayleigh.com Eastern European Office : Rayleigh Instruments Sp. z o.o. ul. Aleje Jerozolimskie 214, 02-486, Warszawa. Poland. Telephone : +48 22 290 27 26 www.rayleigh.pl Rayleigh Instruments Limited www.rayleigh.com...