Mitsubishi Electric PUHZ-P200YKA3 Service Manual page 62

Hide thumbs Also See for PUHZ-P200YKA3:
Table of Contents

Advertisement

Type of
Switch No.
Switch
1
2
SW5
3,4,5
6
1
2
3
4
SW7*
Max Hz setting (heating)
4
5
6
1
SW8
2
DIP
3
switch
1
SW9
2
3,4
1
2
3
4
SW6
5
6
7
8
SW5
6
'Power failure automatic recovery' can be set by either remote controller or this DIP SW. If one of them is set to ON, 'Auto
2
*
recovery' activates. Please set "Auto recovery" basically by remote controller because all units do not have DIP SW.
Please refer to the indoor unit installation manual.
SW7-1 is setting change over of Demand/Low noise. It is effective only in case of external input.
3
*
(Local wiring is necessary. Refer to the next page: Special function)
Please do not use SW7-3 to 7-6 usually. Trouble might be caused by the usage condition.
4
*
SW5-1 to 5: Function switch
5
*
OCH679
Function
No function
Power failure
automatic recovery *
2
No function
Model select
Mode select *
3
No function
Max Hz setting (cooling)
No function
Defrost setting
No function
No function
No function
No function
Function switch
No function
Model select
Action by the switch operation
ON
Auto recovery
Following SW5-6 reference
Demand function
Max Hz (cooling) o 0.8
Max Hz (heating) o 0.8
For high humidity
Valid
The black square (■) indicates a switch position.
MODEL
ON
200Y
OFF
1 2 3 4 5 6 7 8
ON
250Y
OFF
1 2 3 4 5 6 7 8
62
Effective timing
OFF
No auto recovery
When power supply ON
Low noise mode
Normal
Normal
Normal
Normal
SW6
SW5-6 *2
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
Always
Always
Always
Always
Always