Mitsubishi Electric PUHZ-P200YKA3 Service Manual page 10

Hide thumbs Also See for PUHZ-P200YKA3:
Table of Contents

Advertisement

5-5. STANDARD OPERATION DATA
Representative matching
Mode
Capacity
Input
Indoor unit
Phase , Hz
Voltage
Input
Current
Outdoor unit
Phase , Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
SHF
BF
OCH679
PLA-RP100EA.UK ×2
Cooling
W
19,000
kW
5.89
PLA-RP100EA.UK
V
0.07 × 2
kW
A
0.46 × 2
PUHZ-P200YKA3.UK
V
9.18
A
2.95
MPa
0.86
MPa
66.6
°C
49.7
°C
6.9
°C
7.5
m
D.B.
27
°C
W.B.
19
°C
D.B.
10.7
°C
D.B.
35
°C
W.B.
24
°C
0.79
0.11
Heating
22,400
5.99
1, 50
230
0.07 × 2
0.44 × 2
3, 50
400
9.28
2.58
0.63
64.8
44.0
−2.9
7.5
20
15
39.5
7
6
10
PLA-RP125EA.UK ×2
Cooling
Heating
22,000
27,000
6.92
7.26
PLA-RP125EA.UK
1, 50
230
0.10 × 2
0.10 × 2
0.64 × 2
0.66 × 2
PUHZ-P250YKA3.UK
3, 50
400
10.47
10.97
2.56
2.98
0.60
0.88
74.0
68.9
50.2
44.0
−4.1
6.7
7.5
7.5
27
20
19
15
11.6
42.2
35
7
24
6
0.67
0.14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Puhz-p250yka3Puhz-p200yka3.ukPuhz-p250yka3.uk

Table of Contents